It can be dened whether humidity control is active during defrost or not.
Figure 17: Humidier control
Danfoss
80G8221
Humidity
Time
Humidity diff.
SP
Humidifier
100%
If the humidity gets below the SP, then humidication is started via a DO signal to a humidier.
If the humidity increases to SP + humidity dierential, then humidication is stopped.
Figure 18: Dehumidier control
Danfoss
80G8222
Humidity
Time
Humidity diff.
100%
SP
Dehumidifier
If the humidity rises above the SP, then dehumidication is started via a DO signal to a dehumidier.
If the humidity drops below the SP – Humidity dierential, then dehumidication is stopped.
Heating function (only with custom set-up)
The heating function is used to prevent the temperature from becoming too low, e.g. in a cold room, etc. The limit
for when the heating function cuts o is set as an oset value below the current cut-out limit for the refrigeration
thermostat. This ensures that refrigeration and heating do not occur simultaneously. The dierence for the heating
thermostat has the same value as for the refrigeration thermostat. To prevent that the heating thermostat cuts in
during short-term drops in air temperature, a time delay can be set for when to change from refrigeration to
heating.
© Danfoss | Climate Solutions | 2021.02 BC364229688105en-000101 | 19
AK-CC55 Single Coil and Single Coil UI

Table of Contents

Other manuals for Danfoss AK-CC55

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss AK-CC55 and is the answer not in the manual?

Danfoss AK-CC55 Specifications

General IconGeneral
BrandDanfoss
ModelAK-CC55
CategoryController
LanguageEnglish

Related product manuals