Control
Table 24: Control
Function
Values
R-W
Code
1
2
3
4
5
6
7
8
9
Min. value
Max. value
Fact. value
Alarm relay priority
0=Not used, 1=High Priori-
ty, 2=Medium priority,
3=All
1-2
P41
*
*
*
*
*
*
*
0
3
2
Blinds max. open time
1-2
P60
*
0 min
60 min
5 min
Fan stop at blinds closing
1-2
P65
*
*
*
*
*
*
*
*
0 s
300 s
0s
Rail heat PWM - Period
time
1-2
P82
*
*
*
*
*
*
*
*
*
4 s
60 s
10 s
Refrigerant factor K1
1-3
(1)
P83
*
*
*
*
*
*
*
*
*
-999
999
300
Refrigerant factor K2
1-3
(1)
P84
*
*
*
*
*
*
*
*
*
-999
999
300
Refrigerant factor K3
1-3
(1)
P85
*
*
*
*
*
*
*
*
*
-999
999
300
Max. superheat liquid ctrl.
A
1-2
P86
*
*
*
*
*
*
*
*
*
P87
20.0 °C
3.0 °C
Min. superheat liquid ctrl A
1-2
P87
*
*
*
*
*
*
*
*
*
0.0 °C
P86
1.0 °C
Access code 1
1-1
P88
*
*
*
*
*
*
*
*
*
0
999
0
Display lock
0=OFF, 1=ON
1-2
P89
*
*
*
*
*
*
*
*
*
0
1
0
LLSV closing delay
1-2
P92
*
*
*
*
*
*
*
*
0 s
300 s
5 s
(1)
In order to change this parameter the regulation must be stopped via the parameter r12 Main switch = OFF.
(1)
In order to change this parameter the regulation must be stopped via the parameter r12 Main switch = OFF.
DO cong and manual
Table 25: DO cong and manual
Function
Values
R-W
Code
1
2
3
4
5
6
7
8
9
Min. value
Max. value
Fact. value
DO2
Conguration
0=None, 1=Fans, 2=Fan
ECO, 3=Defrost, 4=Rail
heat, 5=Alarm, 6=Light,
7=Blinds, 8=Compressor/
LLSV, 9=Compressor 2,
10=Air heater
1-3
(1)
q02
*
0
10
5
DO3
Conguration
0=None, 1=Fans, 2=Fan
ECO, 3=Defrost, 4=Rail
heat, 5=Alarm, 6=Light,
7=Blinds, 8=Compressor/
LLSV, 9=Compressor 2,
10=Air heater
1-3
(1)
q03
*
0
10
8
DO4
Conguration
0=None, 1=Fans, 2=Fan
ECO, 3=Defrost, 4=Rail
heat, 5=Alarm, 6=Light,
7=Blinds, 8=Compressor/
LLSV, 9=Compressor 2,
10=Air heater
1-3
(1)
q04
*
0
10
9
DO5
Conguration
0=None, 1=Fans, 2=Fan
ECO, 3=Defrost, 4=Rail
heat, 5=Alarm, 6=Light,
7=Blinds, 8=Compressor/
LLSV, 9=Compressor 2,
10=Air heater
1-3
(1)
q05
*
0
10
3
DO6
Conguration
0=None, 1=Fans, 2=Fan
ECO, 3=Defrost, 4=Rail
heat, 5=Alarm, 6=Light,
7=Blinds, 8=Compressor/
LLSV, 9=Compressor 2,
10=Air heater
1-3
(1)
q06
*
0
10
1
AO1
Conguration
0=None, 1=Rail heat PWM,
2=Valve driver
1-3
(1)
q09
*
*
*
*
*
*
*
*
*
0
2
0
EEV override A
1-2
(2)
q11
*
*
*
*
*
*
*
*
*
0 %
100 %
0%
Compressor 1 - override
0=MAN OFF, 1=MAN ON
1-2
(2)
q12
*
*
*
*
0
1
0
Fan - override
0=MAN OFF, 1=MAN ON
1-2
(2)
q13
*
*
*
*
*
*
*
*
*
0
1
0
Defrost A - override
0=MAN OFF, 1=MAN ON
1-2
(2)
q14
*
*
*
*
*
*
*
*
0
1
0
Rail heat - override
0=MAN OFF, 1=MAN ON
1-2
(2)
q15
*
*
*
*
*
0
1
0
Alarm relay - override
0=MAN OFF, 1=MAN ON
1-2
(2)
q16
*
*
*
*
*
*
*
0
1
0
Light - override
0=MAN OFF, 1=MAN ON
1-2
(2)
q17
*
*
*
*
*
*
*
*
0
1
0
Suction valve - override
0=MAN OFF, 1=MAN ON
1-2
(2)
q18
*
0
1
0
Compressor 2 - override
0=MAN OFF, 1=MAN ON
1-2
(2)
q19
*
0
1
0
AK-CC55 Single Coil and Single Coil UI
© Danfoss | Climate Solutions | 2021.02 BC364229688105en-000101 | 44