EasyManua.ls Logo

Danfoss AK-CC55 - Thermostat Control Parameters; Thermostat State, Timing, and Limits; Thermostat Sensor S4% and Night Offset

Danfoss AK-CC55
69 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Thermostat control
Table 29: Thermostat control
Function
Description
Values
Code
Short name
Control state A
Readout of the actual control state of the controller
0=Normal ctrl., 1=Hold after defrost, 2=Min ON timer,
3=Min OFF timer, 4=Drip o, 10=Main switch OFF,
11=Thermostat cut-out, 12=Frost protection S4,
13=Not_used, 14=Defrost, 15=Fan delay, 17=Door
open, 18=Melt period, 19=Modulating temp. control,
20=Emergency control, 23=Adaptive superheat con-
trol, 24=Start injection, 25=Manual control, 26=No re-
frigerant selected, 16=Forced closing, 29=Case clean-
ing, 30=Forced cooling, 31=Door open, 32=Power-up
delay, 33=Air heating, 45=Shut down controller,
48=Adaptive liquid control
u00
u00 Ctrl. state
Thermostat air
temp. A
Thermostat temperature
u17
u17 Ther. air
Food temperature A
Readout of food temperature
U72
U72 Food temp.
S3 Air ON evap. A
Actual sensor value
u12
u12 S3 air temp.
S3 Air ON evap. B
Actual sensor value
u76
u76 S3 airtemp B
S4 Air OFF evap. A
Actual sensor value
u16
u16 S4 air temp.
Night condition
Status of the day/night operation (night operation:
on/o)
0=OFF, 1=ON
u13
u13 Night Cond.
Thermostat cut-in
temp.
Readout of the actual cut-in value for the thermostat
u90
u90 Cutin temp.
Thermostat cut-out
temp.
Readout of the actual cut-out value for the thermo-
stat
u91
u91 Cutout temp.
Thermostat run time
A
Read the ongoing cut-in time for the thermostat or
the duration of the last completed cut-in
u18
u18 Ther runtime
Thermostat band
Readout of which thermostat is used for regula-
tion:1= Thermostat band 12= Thermostat band 2
1=Band 1, 2=Band 2
u86
u86 Ther. band
Air heater
Actual status of output function
0=OFF, 1=ON
u84
u84 Heat relay
Thermostat mode
Here it is dened how the thermostat is to be operat-
ed. Either as an ordinary ON/OFF thermostat or as a
modulating thermostat.When operation is ”modulat-
ing” the valve will limit the ow of refrigerant so that
the temperature variation will be less than for the
ON/OFF thermostat.The thermostat dierential (r01)
must not be set lower than 2K for ""modulating"".In a
decentralised plant you must select the ON/OFF ther-
mostat setting."
1=ON/OFF, 2=Modulating
r14
r14 Therm. mode
Cut-out 1
Setpoint. The thermostat’s cut-out value when the
given thermostat band is in use
r00
r00 Cutout
Cut-out 2
Setpoint. The thermostat’s cut-out value when the
given thermostat band is in use
r21
r21 Cutout 2
Dierential
When the temperature is higher than the set cut-out
+ the set dierential, the compressor relay will be cut-
in. It will cut-out again when the temperature comes
down to the set cut-out limit
r01
r01 Dierential
Max cut-out limit
Setpoint limitation - The controller’s setting range for
the thermostat setpoint may be narrowed down, so
that too high or too low values are not set accidental-
ly - with resulting damages.To avoid a too high set-
ting of the setpoint, the max. allowable reference val-
ue may be lowered
r02
r02 Max cutout
Min cut-out limit
Setpoint limitation - The controller’s setting range for
the thermostat setpoint may be narrowed down, so
that too high or too low values are not set accidental-
ly - with resulting damages.To avoid a too low setting
of the setpoint, the min. allowable reference value
may be increased
r03
r03 Min cutout
Thermostat sensor
S4 %
Selection of thermostat sensor. Here you dene the
sensor that the thermostat is to use for its control
function. S3, S4, or a combination of them. With the
setting 0%, only S3 is used. With 100%, only S4.
r15
r15 Ther. S4 %
Thermostat sensor
S4 % night
Selection of thermostat sensor S4% during night op-
eration with night blinds. Here you dene the sensor
that the thermostat is to use for its control function.
S3, S4, or a combination of them. With the setting 0%,
only S3 is used. With 100%, only S4.
r61
r61 Ther.S4% Ngt
Night oset
Night setback value.The thermostat’s reference will
be the setpoint plus this value when the controller
changes over to night operation.
r13
r13 Night oset
AK-CC55 Single Coil and Single Coil UI
© Danfoss | Climate Solutions | 2021.02 BC364229688105en-000101 | 50

Table of Contents

Other manuals for Danfoss AK-CC55

Related product manuals