Injection control
Table 19: Injection control
Function
Values
R-W
Code
1
2
3
4
5
6
7
8
9
Min. value
Max. value
Fact. value
Max. superheat limit
1-2
n09
*
*
*
*
*
*
*
*
*
n10
20.0 °C
12.0 °C
Min. superheat limit
1-2
n10
*
*
*
*
*
*
*
*
*
2.0 °C
n09
3.0 °C
MOP temperature
1-2
n11
*
*
*
*
*
*
*
*
*
-50.0 °C
15.0 °C
15.0 °C
AKV Period time
1-2
(1)
n13
*
*
*
*
*
*
*
*
*
3 s
6 s
6 s
(1)
In order to change this parameter the regulation must be stopped via the parameter r12 Main switch = OFF.
(1)
In order to change this parameter the regulation must be stopped via the parameter r12 Main switch = OFF.
Fan control
Table 20: Fan control
Function
Values
R-W
Code
1
2
3
4
5
6
7
8
9
Min. value
Max. value
Fact. value
Fan stop high S5 temp.
1-2
F04
*
*
*
*
*
*
*
*
*
-50.0 °C
50.0 °C
50.0 °C
Fan pulsing mode
0=No pulsing, 1=Pulsing
cut-out, 2=Pulsing cut-out
night
1-2
F05
*
*
*
*
*
*
*
*
*
0
2
0
Fan period time
1-2
F06
*
*
*
*
*
*
*
*
*
1 min
30 min
5 min
Fan ON cycle
1-2
F07
*
*
*
*
*
*
*
*
*
0 %
100 %
100%
Defrost schedule
Table 21: Defrost schedule
Function
Values
R-W
Code
1
2
3
4
5
6
7
8
9
Min. value
Max. value
Fact. value
Defrost schedule
0=No, 1=Yes
1-2
t00
*
*
*
*
*
*
*
*
*
0
1
0
Def. start 1 - Hours
1-2
t01
*
*
*
*
*
*
*
*
*
0 h
23 h
0 h
Def. start 1 - Minutes
1-2
t11
*
*
*
*
*
*
*
*
*
0 min
59 min
0 min
Def. start 2 - Hours
1-2
t02
*
*
*
*
*
*
*
*
*
0 h
23 h
0 h
Def. start 2 - Minutes
1-2
t12
*
*
*
*
*
*
*
*
*
0 min
59 min
0 min
Def. start 3 - Hours
1-2
t03
*
*
*
*
*
*
*
*
*
0 h
23 h
0 h
Def. start 3 - Minutes
1-2
t13
*
*
*
*
*
*
*
*
*
0 min
59 min
0 min
Def. start 4 - Hours
1-2
t04
*
*
*
*
*
*
*
*
*
0 h
23 h
0 h
Def. start 4 - Minutes
1-2
t14
*
*
*
*
*
*
*
*
*
0 min
59 min
0 min
Def. start 5 - Hours
1-2
t05
*
*
*
*
*
*
*
*
*
0 h
23 h
0 h
Def. start 5 - Minutes
1-2
t15
*
*
*
*
*
*
*
*
*
0 min
59 min
0 min
Def. start 6 - Hours
1-2
t06
*
*
*
*
*
*
*
*
*
0 h
23 h
0 h
Def. start 6 - Minutes
1-2
t16
*
*
*
*
*
*
*
*
*
0 min
59 min
0 min
Time hours
0-1
t07
*
*
*
*
*
*
*
*
*
0 h
23 h
0 h
Time minutes
0-1
t08
*
*
*
*
*
*
*
*
*
0 min
59 min
0 min
Time date
0-1
t45
*
*
*
*
*
*
*
*
*
1
31
1
Time month
0-1
t46
*
*
*
*
*
*
*
*
*
1
12
1
Time year
0-1
t47
*
*
*
*
*
*
*
*
*
0
100
0
Monday - Follow schedule
0=No, 1=Yes
1-2
t51
*
*
*
*
*
*
*
*
*
0
1
1
Tuesday - Follow schedule
0=No, 1=Yes
1-2
t52
*
*
*
*
*
*
*
*
*
0
1
1
Wednesday - Follow sched-
ule
0=No, 1=Yes
1-2
t53
*
*
*
*
*
*
*
*
*
0
1
1
Thursday - Follow schedule
0=No, 1=Yes
1-2
t54
*
*
*
*
*
*
*
*
*
0
1
1
Friday - Follow schedule
0=No, 1=Yes
1-2
t55
*
*
*
*
*
*
*
*
*
0
1
1
Saturday - Follow schedule
0=No, 1=Yes
1-2
t56
*
*
*
*
*
*
*
*
*
0
1
1
Sunday - Follow schedule
0=No, 1=Yes
1-2
t57
*
*
*
*
*
*
*
*
*
0
1
1
Humidity control
Table 22: Humidity control
Function
Values
R-W
Code
1
2
3
4
5
6
7
8
9
Min. value
Max. value
Fact. value
Humidity cut-in
0-2
h23
*
0 RH%
100 RH%
70RH%
Humidity
dierential
1-2
h24
*
1 RH%
30 RH%
5RH%
Humidity high alarm limit
1-2
h25
*
0 RH%
100 RH%
100RH%
Humidity low alarm limit
1-2
h26
*
0 RH%
100 RH%
0RH%
© Danfoss | Climate Solutions | 2021.02 BC364229688105en-000101 | 41