EasyManuals Logo

Danfoss AK-CC55 User Manual

Danfoss AK-CC55
69 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #62 background imageLoading...
Page #62 background image
Function
Description
Values
Code
Short name
MC Case shutdown
Master control signal used to shut down a case for a
time period. During shutdown there will be no alarm
monitoring
0=OFF, 1=ON
x17
--- Case shutdwn
MC Forced closing
Master control signal that will close the injection
valve
0=OFF, 1=ON
x07
--- Forced close
MC Forced cooling
Master control signal that will provide forced cooling
0=OFF, 1=ON
x08
--- Forced cool.
MC Defrost start
Master control signal for starting a defrost. At adap-
tive defrost the defrost might be skipped if the de-
frost is not needed
0=OFF, 1=ON
x13
--- MC def.start
MC Defrost state
Read out the actual state of the defrost
0=OFF, 1=ON
x14
--- DefrostState
MC Hold after de-
frost
Master control signal used for co-ordinated defrost
control to hold cabinets from returning to normal re-
frigeration after a defrost until all cabinets have termi-
nated defrost
0=OFF, 1=ON
x11
--- HoldAfterDef
MC Stop defrost
Master control signal used to prevent a defrost start
in a controller.
0=OFF, 1=ON
x12
--- Disable def.
MC Request next
defrost
Master control signal used by system manager to see
if a controller is requesting that the next defrost has
to be carried out
0=No, 1=Yes
x94
--- AD def.req.
MC Light signal
Master control signal for control of light via a data
communication signal from the system manager
0=OFF, 1=ON
o39
o39 Light remote
MC Actual dewpoint
Master control signal sending the actual measured
dewpoint from the system manager to the controller
over the network.
x03
--- Act.DewPoint
MC Tc temp. mean
Master control signal distributing the condensing
temperature signal to the case controllers that are us-
ing adaptive defrost. At transcritical CO2 sites the re-
ceiver pressure is distributed to the case controllers.
This function needs to be set up in the system man-
ager.
x04
--- TcTempMean
MC Po load factor
x83
--- Load factor
MC Bluetooth lock
Master control signal that will lock down all Bluetooth
data communication
0=OFF, 1=ON
aaa
--- BT lock
MC Min. delta T
Required minimum delta temperature across evapo-
rator (S3 - Te) in order to keep the air temperature at
the actual setpoint
y04
--- Min Delta T
Fault message
In an error situation the alarm LED on the front will be on and the alarm relay will be activated (depending on
priority). If you push the alarm button for 3 seconds you can see the alarm report in the display. (Alarm priorities can
be changed. See Table 40: Alarm relay priorities.) Here are the messages that may appear:
Table 48: Fault message
Code
Alarm text
Description
E01
Hardware failure
The controller has a hardware failure
E06
Clock lost time
Clock has lost valid time
E20
Pe Evap. pressure A - Sensor error
Sensor signal is out of range. Please check the sensor for correct operation
E24
S2 Gas outlet A - Sensor error
Sensor signal is out of range. Please check the sensor for correct operation
E25
S3 Air ON evap. A - Sensor error
Sensor signal is out of range. Please check the sensor for correct operation
E26
S4 Air OFF evap. A - Sensor error
Sensor signal is out of range. Please check the sensor for correct operation
E27
S5 Evaporator A - Sensor error
Sensor signal is out of range. Please check the sensor for correct operation
E28
S6 product temp. A - Sensor error
Sensor signal is out of range. Please check the sensor for correct operation
E34
S3 Air ON evap. B - Sensor error
Sensor signal is out of range. Please check the sensor for correct operation
E37
S5 Evaporator B - Sensor error
Sensor signal is out of range. Please check the sensor for correct operation
E59
Humidity sensor - Sensor error
Sensor signal is out of range. Please check the sensor for correct operation
A01
High temperature alarm A
The alarm temperature has been above the max alarm limit for a longer time period than the set alarm de-
lay.
A02
Low temperature alarm A
The alarm temperature has been below the min alarm limit for a longer time period than the set alarm de-
lay.
A04
Door open alarm
The door has been open for a too long time
A05
Max defrost hold time exceeded
The controller has been waiting longer time than permitted after a co-ordinated defrost.
A11
Refrigerant not selected
The refrigerant has not been selected hence control can not be initiated
A13
S6 high product temperature A
The S6 Product temperature has been above the max alarm limit for a longer time period than the set alarm
delay.
AK-CC55 Single Coil and Single Coil UI
© Danfoss | Climate Solutions | 2021.02 BC364229688105en-000101 | 62

Table of Contents

Other manuals for Danfoss AK-CC55

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss AK-CC55 and is the answer not in the manual?

Danfoss AK-CC55 Specifications

General IconGeneral
BrandDanfoss
ModelAK-CC55
CategoryController
LanguageEnglish

Related product manuals