Function
Values
R-W
Code
1
2
3
4
5
6
7
8
9
Min. value
Max. value
Fact. value
DI2 Conguration
0=None, 1=DI status,
2=Door function, 3=Door
alarm, 4=Defrost start,
5=Main switch, 6=Night
setback, 7=Thermostat
band, 8=Alarm at closed,
9=Alarm at open, 10=Case
cleaning, 11=Forced cool-
ing, 12=Open blinds,
13=Coordinated defrost,
14=Forced closing,
15=Shutdown, 16=Light
control, 20=Leak detection,
21=Adaptive liquid control,
22=Valve driver, 23=Fan
alarm
1-2
(1)
o37
*
*
*
*
*
*
*
*
*
0
23
0
Light control mode
1=Day and night, 2=Net-
work, 3=Door switch,
4=Network (Fallback),
5=Digital input
1-2
o38
*
*
*
*
*
*
*
*
1
5
1
MC Light signal
0=OFF, 1=ON
1-2
o39
*
*
*
*
*
*
*
*
0
1
0
Rail heat ON cycle day
1-2
o41
*
*
*
*
*
*
*
*
*
0 %
100 %
100%
Rail heat ON cycle night
1-2
o42
*
*
*
*
*
*
*
*
*
0 %
100 %
100%
Rail heat period time
1-2
o43
*
*
*
*
*
6 min
60 min
6 min
Case cleaning mode
0=OFF, 1=Fans run,
2=Cleaning
0-1
o46
*
*
*
*
*
*
*
*
*
0
2
0
Application mode
1=1. Comp/Alarm/Light,
2=2. Comp/Rail/Light, 3=3.
Comp/Alarm/Rail, 4=4.
Alarm/Rail/Light, 5=5. Hot
gas remote, 6=6. Dual with
1 evap., 7=7. Dual with 2
evap., 8=8. Cold room, 9=9.
Custom
1-3
(1)
o61
*
*
*
*
*
*
*
*
*
1
9
1
Access code 2
2-2
o64
*
*
*
*
*
*
*
*
*
0
999
0
Make new factory
0=OFF, 1=ON
3-3
(1)
o67
*
*
*
*
*
*
*
*
*
0
1
0
DI3 Conguration
0=None, 1=DI status,
2=Door function, 3=Door
alarm, 4=Defrost start,
5=Main switch, 6=Night
setback, 7=Thermostat,
band, 8=Alarm at closed,
9=Alarm at open, 10=Case
cleaning, 11=Forced cool-
ing, 12=Open blinds,
13=Coordinated defrost,
14=Forced closing,
15=Shutdown, 16=Light
control, 20=Leak detection,
21=Adaptive liquid control,
22=Valve driver, 23=Fan
alarm
1-2
(1)
o84
*
*
*
*
*
*
*
*
*
0
23
0
Rail heat control mode
0=ON, 1=Day/Night timer,
2=Dewpoint ctrl.
1-2
o85
*
*
*
*
*
*
*
*
*
0
2
0
Dewpoint min. limit
1-2
o86
*
*
*
*
*
*
*
*
*
-10.0 °C
o87
8.0 °C
Dewpoint max. limit
1-2
o87
*
*
*
*
*
*
*
*
*
o86
50.0 °C
17.0 °C
Rail heat min. ON cycle
1-2
o88
*
*
*
*
*
*
*
*
*
0 %
100 %
30%
Door restart inj. delay
1-2
o89
*
*
*
*
*
*
*
*
*
0 min
240 min
30 min
Fan at forced closing
0=OFF, 1=ON, 2=OFF and
suppress defrost, 3=ON
and suppress defrost
1-2
o90
*
*
*
*
*
*
*
*
*
0
3
1
Display readout
1=Display air, 2=S6 Product
temp.
1-2
o97
*
*
*
*
*
*
*
1
2
1
Light at Main switch OFF
0=OFF, 1=Normal ctrl.
1-2
o98
*
*
*
*
*
*
*
*
0
1
0
(1)
In order to change this parameter the regulation must be stopped via the parameter r12 Main switch = OFF.
(1)
In order to change this parameter the regulation must be stopped via the parameter r12 Main switch = OFF.
© Danfoss | Climate Solutions | 2021.02 BC364229688105en-000101 | 43