Open parameter r89 and set the number for the array of presettings. The few selected settings will now be
transferred to the menu
Set the desired cut-out temperature r00
Select refrigerant via parameter o30
Set the pressure transmitter min. and max. range via parameter o20 and o21
Set the desired defrost method in d01
Set the interval time between defrost starts in d03
Set the desired defrost sensor in d10
Set the maximum defrost time in d04
Set the defrost stop temperature in d02
Open parameter r12 and start the regulation
Go through the parameter list and change the factory values where needed
Get the controller up and running on network:
◦ MODBUS: Activate scan function in system unit
◦ If another data communication card is used in the controller:
▪ Lon RS485: Activate the function o04
▪ Ethernet: Use the MAC address
Table 14: Food type settings
Setting of presettings (r89).
After setting 1-5, setting is returned to 0.
Upper alarm limit for S6 (A22)
Lower alarm limit for S6 (A23)
Can only be set when r12=0.