Table 16: Brake Cable Size Recommendations, 380–500 V (continued)
Model code Frame I
N
[A]
Cable [mm
2
]
Maximum
cable size
[mm
2
]
Maximum
number of
brake cables
Bolt size
iC7-60EA3N05-4
80A
480 Cu 2 x (3x120+70)
Al 2 x (2x185+57 Cu)
240 2 M10
iC7-60EA3N05-5
88A
FE10
588 Cu 2 x (3x150+70)
Al 2 x (3x240+41 Cu)
240 2 M10
6.2.7 Brake Cable Size Recommendations, UL
Model code Frame I
N
[A] Cable AWG Maximum
cable size
[mm
2
]
Maximum
number of
brake cables
Bolt size
iC7-60EA3N
05-206A
206 2 x 4/0 4/0 2 per polarity M10
iC7-60EA3N
05-245A
245 2 x 4/0 4/0 2 per polarity M10
iC7-60EA3N
05-302A
302 2 x 4/0 4/0 2 per polarity M10
iC7-60EA3N
05-385A
FE9
385 2 x 4/0 4/0 2 per polarity M10
iC7-60EA3N
05-480A
480 2 x 400 MCM 400 MCM 2 M10
iC7-60EA3N
05-588A
FE10
588 2 x 400 MCM 400 MCM 2 M10
6.3 Fuses
6.3.1 Fuse Size Tables
The fuse size tables for the air-cooled enclosed drives can be found with these links.
l
6.3.2 AC Fuses, 380–500 V AC
l 6.3.3 DC Fuses, 465–800 V DC
l 6.3.4 External Fuses on External Supply for Input Devices
42 | Danfoss Drives Oy © 2024.09 AN484843731544en-000101 / 172K4825A