6.3.3 DC Fuses, 465–800 V DC
Table 18: DC Fuses, 465–800 V DC
Model code Frame Rated
current I
L
[A]
Number of
fuses
Fuse size Part number Fuse U
n
[V]
Fuse I
n
[A]
iC7-60EA3A05-385A 385 2 73 PC73UD13C630TF 1250 630
iC7-60EA3A05-480A 480 2 73 PC73UD13C800TF 1250 800
iC7-60EA3A05-590A
AE10 +
IE10
590 2 73 PC73UD10C1000TF 1000 1000
iC7-60EA3A05-658A 658 2 73 PC73UD90V13CTF 900 1250
iC7-60EA3A05-730A 730 2 73 PC73UD90V13CTF 900 1250
iC7-60EA3A05-820A 820 2 73 PC73UD85V14CTF 850 1400
iC7-60EA3A05-880A
AE11 +
IE11
880 2 73 PC73UD85V14CTF 850 1400
iC7-60EA3A05-1000 1000 8 73 PC73UD13C800TF 1250 800
iC7-60EA3A05-1100
2xAE10 +
2xIE10
1100 8 73 PC73UD10C1000TF 1000 1000
iC7-60EA3A05-1260 1260 8 73 PC73UD90V13CTF 900 1250
iC7-60EA3A05-1450 1450 8 73 PC73UD90V13CTF 900 1250
iC7-60EA3A05-1710
2xAE11 +
2xIE11
1707 8 73 PC73UD85V14CTF 850 1400
6.3.4 External Fuses on External Supply for Input Devices
The enclosed drives with a mains contactor or a main switch must be protected with external fuses. The fuses in the table meet the IEC
type 1 coordination for contactor short-circuit current performance and are required for main switch protection.
Table 19: External Fuses of the Enclosed Drives
Model code Frame IEC fuse Maximum UL fuse
iC7-60EA3N05-206A gG 315 A
(1)
or gG 355 A Class J, 500 A
iC7-60EA3N05-245A gG 315 A Class J, 500 A
iC7-60EA3N05-302A gG 400 A Class J, 500 A
iC7-60EA3N05-385A gG 500 A Class J, 500 A
iC7-60EA3N05-480A Class J, 600 A
iC7-60EA3N05-588A
FE9, FE10
gG 630 A
Class J, 600 A
iC7-60EA3A05-385A
iC7-60EA3A05-480A
–
iC7-60EA3A05-590A
AE10 + IE10 gG 630 A
–
44 | Danfoss Drives Oy © 2024.09 AN484843731544en-000101 / 172K4825A
Installation Guide | iC7-Automation Air-cooled Enclosed Drives Specifications