Table 8: Relay 1 Signals (X101)
Terminal Function Terminal block Description
1 COM XD2.1:1
2 NO XD2.1:2
3 NC XD2.1:3
Configurable relay output.
Switching capacity:
• 24V DC/8A
• 250V AC/8A
• 125V DC/0.4A
Minimum switching load: 5V/10mA
Table 9: Relay 2 Signals (X102)
Terminal Function Terminal block Description
4 COM XD2.1:4
5 NO XD2.1:5
6 NC XD2.1:6
Configurable relay output.
Switching capacity:
• 24V DC/8A
• 250V AC/8A
• 125V DC/0.4A
Minimum switching load: 5V/10mA
Table 10: Relay 3 Signals (X103)
Terminal Function Terminal block Description
7 COM XD2.1:7
8 NO XD2.1:8
Configurable relay output.
Switching capacity:
• 24V DC/8A
• 250V AC/8A
• 125V DC/0.4A
Minimum switching load: 5V/10mA
4.3 Control Cable Routing
Use the control cable grommets and tubes to route the control cables into the control compartment. There are control cable grommets
at the top and at the bottom of the cabinet.
22 | Danfoss Drives Oy © 2024.09 AN484843731544en-000101 / 172K4825A
Installation Guide | iC7-Automation Air-cooled Enclosed Drives Control and Option Installation