EasyManua.ls Logo

Danfoss iC7 - Specifications; Tightening Torques; Cable Sizes; List of Cable Size Information

Danfoss iC7
48 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6 Specifications
6.1 Tightening Torques
Table 11: Tightening Torques
Tightening torqueFrame Bolt
Nm In-lb
M4 1.8 16
M5 2.7 24
FE9, FE10
M6 6 53
M8 20 180FE9, FE10, AE10, AE11, IE10, IE11
M10 40 350
M12 70 620FE9, FE10, AE10, AE11, IE10, IE11
Grounding bolt (M8) 13.5 120
6.2 Cable Sizes
6.2.1 List of Cable Size Information
NOTICE
Use symmetrical cabling with system modules connected in parallel. Each module must have the same number of cables with an
equal cross-section.
The cable size tables for the enclosed drives can be found with these links.
l
6.2.2 Mains Cable Size Recommendations, 380–500 V
l 6.2.3 Motor Cable Size Recommendations, 380–500 V
l 6.2.4 Mains Cable Size Recommendations, UL 480 V
l 6.2.5 Motor Cable Size Recommendations, UL 480 V
l 6.2.6 Brake Cable Size Recommendations
l 6.2.7 Brake Cable Size Recommendations, UL
34 | Danfoss Drives Oy © 2024.09 AN484843731544en-000101 / 172K4825A
Installation Guide | iC7-Automation Air-cooled Enclosed Drives Specifications

Table of Contents