6.2.4 Mains Cable Size Recommendations, UL 480 V
Table 14: Mains Cable Size Recommendations, UL 480 V
Model code Frame I
N
[A] Mains cable
[AWG]
Cable
termination,
Panduit
terminal part
number
Maximum
cable size
Maximum
number of
mains cables
(1)
(hole size of
the mains
terminal
[mm])
Number of
grounding
holes on PE
busbar (hole
size [mm])
iC7-60EA3N05-
206A
206 2 x 1/0 LCAX1/0-12-X 300MCM 2 (Ø10.5) 2 (Ø10.5)
iC7-60EA3N05-
245A
245 2 x 2/0 LCAX2/0-12-X 300MCM 2 (Ø10.5) 2 (Ø10.5)
iC7-60EA3N05-
302A
302 2 x 4/0 LCAX4/0-12-X 300MCM 2 (Ø10.5) 2 (Ø10.5)
iC7-60EA3N05-
385A
FE9
385 2 x 300 MCM LCAX300-12-6 300MCM 2 (Ø10.5) 2 (Ø10.5)
iC7-60EA3N05-
480A
480 3 x 4/0 LCAX4/0-12-X 300MCM 3 (Ø13.5) 4 (Ø10.5)
iC7-60EA3N05-
588A
FE10
588 3 x 300 MCM LCAX300-12-6 300MCM 3 (Ø13.5) 4 (Ø10.5)
iC7-60EA3A05-
385A
303 2 x 4/0 LCAX4/0-12-X 500MCM - (Ø13.5) 4 (Ø10.5)
iC7-60EA3A05-
480A
352 2 x 250 MCM LCAX250-12-X 500MCM - (Ø13.5) 4 (Ø10.5)
iC7-60EA3A05-
590A
AE10 + IE10
451 3 x 4/0 LCAX4/0-12-X 500MCM - (Ø13.5) 4 (Ø10.5)
iC7-60EA3A05-
658A
500 3 x 250 MCM LCAX250-12-X 500MCM 4 (Ø10.5) 5 (Ø10.5)
iC7-60EA3A05-
730A
554 3 x 300 MCM LCAX300-12-6 500MCM 4 (Ø10.5) 5 (Ø10.5)
iC7-60EA3A05-
820A
604 3 x 350 MCM LCAX350-12-6 500MCM 4 (Ø10.5) 5 (Ø10.5)
iC7-60EA3A05-
880A
AE11 + IE11
704 4 x 250 MCM LCAX250-12-X 500MCM 4 (Ø10.5) 5 (Ø10.5)
iC7-60EA3A05-
1000
755 4 x 300 MCM LCAX300-12-6 500MCM 4 (Ø10.5) 5 (Ø10.5)
iC7-60EA3A05-
1100
2xAE10 +
2xIE10
855 4 x 350 MCM LCAX350-12-6 500MCM 4 (Ø10.5) 5 (Ø10.5)