Table 13: Motor Cable Size Recommendations, 380–500 V (continued)
Model
code
Frame I
N
[A]
Cable [mm
2
]
Maximum
cable size
[mm
2
]
(1)
Maximum
number
of motor
cables
Bolt size
(2)
Number of
grounding
holes on PE
busbar
Hole size
of the
grounding
terminal
[mm]
iC7-60EA3A
05-658A
672 Cu 2 x (3x185+95)
Al 3 x (3x150+70
Cu)
240 Cu/Al 4 M10 4 Ø10.5
iC7-60EA3A
05-730A
746 Cu 3 x (3x150+70)
Al 4 x (3x120+41
Cu)
240 Cu/Al 4 M10 4 Ø10.5
iC7-60EA3A
05-820A
838 Cu 3 x (3x150+70)
Al 4 x (3x150+70
Cu)
240 Cu/Al 4 M10 4 Ø10.5
iC7-60EA3A
05-880A
AE11 +
IE11
899 Cu 4 x (3x120+70)
Al 4 x (3x150+70
Cu)
240 Cu/Al 4 M10 4 Ø10.5
iC7-60EA3A
05-1000
1021 Cu 4 x (3x150+70)
6 x (3x95+29 Cu)
240 Cu/Al 8 M10 8 Ø10.5
iC7-60EA3A
05-1100
2 x AE10 +
2 x IE10
1123 Cu 4 x (3x185+95)
Al 6 x (3x120+41
Cu)
240 Cu/Al 8 M10 8 Ø10.5
iC7-60EA3A
05-1260
1287 Cu 6 x (3x120+70)
Al 6 x (3x150+70
Cu)
240 Cu/Al 8 M10 8 Ø10.5
iC7-60EA3A
05-1450
1481 Cu 6 x (3x150+70)
Al 6 x (3x185+57
Cu)
240 Cu/Al 8 M10 8 Ø10.5
iC7-60EA3A
05-1710
2 x AE11 +
2 x IE11
1746 Cu 6 x (3x185+95)
Al 8 x (3x150+70
Cu)
240 Cu/Al 8 M10 8 Ø10.5
1) With the vertical PE busbar extension installed: 20 x Ø6.5 mm or 16 x Ø6.5 mm + 4 x Ø10.5 mm
2) If the option Top-entry +KDOT is used, the bolt size is M13.
3) If the option Top-entry +KDOT is used, the maximum cable size is 240 mm
2
.
4) If the option Top-entry +KDOT is used, the maximum number of motor cables is 4.
38 | Danfoss Drives Oy © 2024.09 AN484843731544en-000101 / 172K4825A
Installation Guide | iC7-Automation Air-cooled Enclosed Drives Specifications