6.2.2 Mains Cable Size Recommendations, 380–500 V
Table 12: Mains Cable Size Recommendations, 380–500 V
Model
code
Frame I
N
[A]
Cable [mm
2
]
Maximum
cable size
[mm
2
]
Maximum
number
of mains
cables
(1)
Hole size of
the mains
terminal
[mm]
Number of
grounding
holes on PE
busbar
Hole size
of the
grounding
terminal
[mm]
iC7-60EA3N
05-206A
206 Cu 1 x (3x70+35)
Al 1 x (3x120+41
Cu)
95 Cu/Al 2 Ø10.5 2 Ø10.5
iC7-60EA3N
05-245A
245 Cu 1 x (3x95+50)
Al 1 x (3x150+41
Cu)
95 Cu/Al 2 Ø10.5 2 Ø10.5
iC7-60EA3N
05-302A
302 Cu 1 x (3x120+70)
Al 2 x (3x95+29 Cu)
95 Cu/Al 2 Ø10.5 2 Ø10.5
iC7-60EA3N
05-385A
FE9
(2)
385 Cu 2 x (3x95+50)
Al 2 x (3x120+41
Cu)
95 Cu/Al 2 Ø10.5 2 Ø10.5
iC7-60EA3N
05-480A
480 Cu 2 x (3x120+70)
Al 2 x (2x185+57
Cu)
150 Cu/120
Al
3 Ø13.5 4 Ø10.5
iC7-60EA3N
05-588A
FE10
(2)
588 Cu 2 x (3x150+70)
Al 2 x (3x240+41
Cu)
150 Cu/120
Al
3 Ø13.5 4 Ø10.5
iC7-60EA3A
05-385A
325 Cu 1 x (3x150+70)
Al 2 x (3x95+29 Cu)
240 Cu/Al 2
(4)
Ø13.5
(5)
4 Ø10.5
iC7-60EA3A
05-480A
403 Cu 2 x (3x95+ 50)
Al 2 x (3x120+41
Cu)
240 Cu/Al 2
(4)
Ø13.5
(5)
4 Ø10.5
iC7-60EA3A
05-590A
AE10 +
IE10
(3)
508 Cu 2 x (3x120+70)
Al 2 x (3x150+41
Cu)
240 Cu/Al 2
(4)
Ø13.5
(5)
4 Ø10.5
Danfoss Drives Oy © 2024.09 AN484843731544en-000101 / 172K4825A | 35