18 Manual RS.8A.N5.02 © Danfoss 10-2007 m2 Version 3.11
Setting the Log Action
Setting the Graph Action
Log printouts are available for selected points on a timed or demand basis
via the print menu. When a log is printed only points with the log action eld
appropriately set will be output. The available settings are:
O Set this point to OFF if you do not want this point to be
shown on any log printouts.
Timed The point will be automatically logged after a specied
time delay.
Manual The point will be logged on demand only.
On Set this option to ON if you require this point to be
shown on the timed log printouts and also on log on
demand printouts.
Repeatedly press to cycle through the elds until the Log eld is highlighted.
Use the ' ' or ' ' keys to set the required log action and press to move the
cursor onto the next eld.
Graph printouts are available for selected points on a timed or demand basis via
the print menu. When a graph is printed only points with the graph action eld
appropriately set will be output. The available settings are:
O Set this option to OFF if you do not want this point
graph to be shown on any graph printouts.
Timed The graph for this point will be automatically printed
after a the time specied in the Log/Graph Setup screen.
Manual The graph for the point will be printed on demand
only.
On Set this option to ON if you require a graph for this
point to be printed after the time specied in the Log/Graph
Setup screen and also on graph on demand’ printouts.
Repeatedly press to cycle through the elds until the Graph eld is
highlighted. Use the ' ' or ' ' keys to set the required graph action.
With the Graph eld highlighted, press and hold down the key until the
second Point Setup screen is displayed or press the ' ' in the point type eld.
The point number and name are the same as those described in rst Point Setup
screen and cannot be edited here.
Use this eld to specify whether the input is connected directly to the m2
master unit (Local), via a m2+ or third party controller (T-Party) or (Remote) via
a EKC controller (Echelon). The input source can be set by pressing the or
keys to the required option. By default the rst 16 points are programmed
to use the 16 local inputs. This conguration is not xed and may be changed.
Press the key to move onto the next eld.
If T-Party has been specied for the Input Source, then this eld is used to
specify the remote address (refer to relavent controller manual or the m2
Instructions RI.8B.M for the m2+ units). If 'Echelon' has been specied for the
Input Source, then this eld is not accessible as it is set from the EKC controller.
Input Source
Point Setup (Screen 2)
Remote Addr