30  Manual  RS.8A.N5.02  ©  Danfoss  10-2007  m2  Version 3.11
Conguring The m2+ Via The Key Pad
The controller's parameters can also be modied using a PC connected to the 
m2 running Danfoss Central Station software. Refer to manual RS.8C.G for more 
information.
To congure a point to a m2+, select the Point Setup option from the Setup 
menu and then select a point number to be used.
The standard point setup screen is then displayed with the standard elds as 
previously described. Use all the elds as previously described except for the 
following:
Set this eld to either 'RTD' (for temperature monitoring) or '420' (for 4-20mA 
inputs).
With the 'Type' eld highlighted, press the ' ' key to display the second point 
setup screen.
Set this eld to  'T-PARTY'.
Set this eld to the same address that has been set on the m2+.
Set this eld to the type of input being used by the m2+ unit.
Use the ‘ ’and ‘ ’ keys to cycle through the valid options as follows:
 
·  RESISTOR  Resistor input.
·  CURRENT  4 - 20 mA input. 
·  DIGITAL  Normally open or normally closed contacts (Contact).
·  PT1000   PT1000 
Set this eld to the input number being used on the m2+ unit for monitoring.
Type
Input Source
Remote Addr
Input Type
Input Number
Remote Controller Parameters