22  Manual  RS.8A.N5.02  ©  Danfoss  10-2007  m2  Version 3.11
The sample frequency aects the amount of data that will be stored in the units 
memory.
  TDays  = Total number of days stored in memory
  Freq  = Graph sample frequency
  Pt  = Highest point number used
  Total  = Total memory available  - 2Mb = 2097152
            - 4Mb = 4194304
            - 6Mb = 6291456
            - 8Mb = 8388608 
    TDays = Freq x (Total - 464000)
        1440 x (6+(2 x Pt))
    Freq = 1440 x TDays x ((2 x Pt)+6)
        Total - 464000
Example table for days using 40 points.
  Freq    Days
  1    47
  2    94
  5    235
  10    471
  15    706
Example table for frequency using 40 points.
  Days    Freq (in minutes)
  100    2
  200    4
  300    6
  500    11
  700    15
These calculations can alter if a large amount of alarms are stored.
Use this option to dene the action to take place when an alarm occurs.  From 
the Setup Menu, select the Alarm Action Setup option.
Use the ‘ ’ or ‘ ’ keys to cycle through the devices and complete the elds for 
each device as described below.
  RELAY 1    MODEM 2
  RELAY 2    MODEM 3
  SIREN      MODEM 4
  LAMP      MODEM 5
  FLASH      PRINT
  MODEM 1
Type in up to 8 characters as an appropriate name for the output device.  Use ‘
’ or ‘ ’ keys to cycle through the character list and the ‘ ‘ or ‘ ‘ key to move 
the cursor left or right respectively.
You can use the ‘ ‘ and ‘ ‘ keys together to delete the character before the 
cursor and ‘ ‘ to change case.  Press ‘↵’ to move onto the next eld.
Use this eld to specify when the device is to be used.  Set the trigger as follows 
for each of the Alarm Actions:
  0  Always OFF (Never trigger)
  1  Always ON (day and night) (Always trigger)
  D  ON during the day (Trigger during the day only)
  N  ON during the night (Trigger during the night only)
Output Name
Action n
Alarm Action Setup