m2 Version 3.11  Manual  RS.8A.N5.02  ©  Danfoss  10-2007  21
Defrosts per  This eld only becomes active if ‘Master’ is selected in the  
Day    previous eld. Enter the amount of defrosts per day      
    required, then whether the times are to be set ‘Manually’   
    or ‘Auotmatically’.
    Manual -  all defrost times entered manually.
    Auto -  select the number of defrosts per day, enter    
      the rst defrost time, then the remaining    
      times will be calculated for a 24 hour period.
Day Night  Select either ‘Yes’ or ‘No’ depending on whether the Day/ 
Control  Night Control on the controller is to be activated of not.
This option allows you to change the three dierent levels of passcodes – Main, 
Local and User, also the Inhibit Protection can be activated.  The Main and Local 
Passcode provides access to all the setup screens.  The User Passcode only 
provides access to the Time/Date setup.
From the Setup Menu, select the Password Setup option.
Use the ‘↵’ to highlight the passcode to be modied.  Type in the passcode 
using the ‘ ’ or ‘ ’ keys to cycle through the character list and the ‘ ’ or ‘
’ key to move the cursor left or right respectively. N.B. Local passcode is 
numeric only. 
You can use the ‘ ‘ and ‘ ’ keys together to delete the character before the 
cursor and ‘ ‘ to change case.  When the passcode has been set, press ‘↵’ then ‘
’ to return to the Setup Menu.
To set the Inhibit Protection, use the ‘↵’ key to highlight the 'Inhibit Protected' 
eld, then using the ‘ ’ or ‘ ’ keys to select either 'Yes' or 'No'.
To set the Point Oset Passcode Disable, use the ‘↵’ key to highlight the ‘Pt 
Oset Disable’ eld in the Passcode Setup menu, then using the ‘ ’ or ‘ ’ keys 
select either ‘Yes’ or ‘No’.
To set the print frequencies, select the Log/Chart Frequency option from the 
Setup Menu.
Use the ‘↵’ to highlight the eld to be modied.  Type in the time required using 
the ‘ ’and ‘ ’ keys to cycle through the character list and the ‘ ’ or ‘ ’ key to 
move the cursor left or right respectively.
Set the values as follows:
Log Print Interval  Set this value to determine the interval between    
      log prints (hours : minutes).
 
Start Print at    Enter the time in the day in which you require the    
      printing of the automatic log readings to start. (Only  
      points that have been set as Timed or ON will be    
      printed).
 
Graph Print Interval  Set this value to determine the interval      
      between  graph prints.
 
Start Print at    Enter the time in the day that you require the    
      automatic graph to be printed.  (Only points that    
      have been set as Timed or ON will be printed.)
Sampling Rate  Set this eld to the frequency of sampling      
      required for the graphs. 
Setting the Log/Chart Frequency
Password Setup
Point Oset Passcode Protection