34 Manual RS.8A.N5.02 © Danfoss 10-2007 m2 Version 3.11
Alarm Action Setup
When an alarm occurs, a number of settings will determine which func-
tions are to be activated.
The denition of each point includes assigning an action number from
1 to 15.
The latter menu display is used to determine which functions will be
activated by the action number in question.
Action-
number
Pressing “Mute” results in alarm reset 1 2 3 4 5 6 7 8
Pressing “Mute” results in alarm reset and alarm reset for AKM 9 10 11
As above, but also transmits alarm status 0 to AKM, if the alarm turns itself
o
12 13 14 15
Action number for use in setting the trigger 1 2 3 4 5 6 7 8
Function
Relay 1
Trigger settings
1 1 1
Relay 2
Siren 1 1 1 1 1 1 1 1
Lamp 1 1 1 1 1 1 1 1
Flash 1 1 1 1 1 1 1 1
Dial O. 1 1 D
Dial O. 2 1 D
Dial O. 3 1 D
Dial O. 4 1 D
Dial O. 5 1 D
Print 1 1 1 1 1 1 1 1
The trigger settings shown are factory settings,
but these can be changed as required.
Settings have the following function:
0: No action
1: Action
D: Action, but only for the day period
N: Action, but only for the night period
The day and night denition is set using the
display “SYSTEM TIME SETUP.
The lines Dial Out 1 to 5 will
only be visible if “Modem” is
selected in the menu AK Com-
munication Setup.
Modem Dial Out Settings
Device: Settings Description
Relay 2: Trigger: 000000000 Enables modem power control