m2 Version 3.11  Manual  RS.8A.N5.02  ©  Danfoss  10-2007  33
Choice of measurements to be displayed as pri-
mary and secondary:
Select the menu: Setup Menu \ Point Setup
Number: Select the point number (i.e. address 
number of EKC)
Type:  Select “EKC”
Alarms:   Will always be “Remote”. The alarm limits 
for the controller will be used.
Other settings are those normally used for m2.
Next menu
Press and hold down the ‘Enter’ key until the second Point Setup screen is 
displayed or press the ' ' in the point type eld.
Input Source:   Select “ECHELON” (= data communication)
Primary Temp:  Used to select the parameter to be displayed 
  as primary 
Secndary Temp: Used to select the parameter to be displayed 
  as secondary
Other settings are those normally used for m2.