m2 Version 3.11  Manual  RS.8A.N5.02  ©  Danfoss  10-2007  19
Input Type
Input Number
Y Axis
Y Base
4 - 20 mA Inputs
Use the ‘ ’ or ‘ ’ keys to cycle through the character list to the required value 
and the ‘ ’ or ‘ ’ key to move the cursor left or right respectively.  Press the ‘↵’ 
key to move onto the next eld.
Use the ‘ ’and ‘ ’ keys to cycle through the valid options as follows:
 
·  RESISTOR  Resistor input.
·  CURRENT  4 - 20 mA input. 
·  DIGITAL  Normally open or normally closed  contacts (Contact).
·  PT1000   PT1000 
This eld is to specify the input number of the (Remote) third party controller or 
m2+ unit.
Use the ‘ ’ or ‘ ’ keys to cycle through the character list to the required value 
and the ‘ ’ or ‘ ’ key to move the cursor left or right respectively.  Press the ‘↵’ 
key to move onto the next eld.
This eld refers to the overall size of the graph temperature range.  Entering 
zero selects the auto-scale option.  Alternatively, enter the required range.  The 
range goes from the lowest graph point (Y Base value) to the highest graph 
point.  Use the ‘ ’, ‘ ’, ‘ ’ or '‘ ’ keys to enter the required value.
This eld refers to the lowest value the graph will show.  This value should be 
slightly lower than you expect the temperature to drop to. If auto scale in the Y 
axis is selected this value is not used.  Use the ‘ ’, ‘ ’, ‘ ’ or '‘ ’ keys to enter 
the required value.
These values are used exclusively in conjunction with a standard 4-20 mA input 
which can represent pressure, humidity, level, ow rate, or any other variable 
which can produce a 4-20 mA output.
The value for the upper and lower limits can therefore represent % (RH), PPM, 
bar or psi etc., depending on the medium being measured.  A numerical 
value for 4 mA (lower limit) and 20 mA (higher limit) is entered, and the m2 
automatically scales the input for a gure proportional to the measurement.  
Use the ‘ ’, ‘ ’, ‘ ’ and ‘ ’ keys to enter the required value.
Finally, press ‘ ’ to return to the Setup Menu.
To  setup the pulsed input, from the Point Setup menu select ‘PLS’ in the Point 
Type eld. All the remaining elds in ‘Screen 1’ of the Point Setup are the same 
as normal.
In ‘Screen 2’ of the Point Setup there are a couple of extra elds added. These 
are as explained below:
This eld is to set either the ‘Constant’ or ‘Peak’ value to be used as explained 
previously.
This eld is to set the amount of pulses that is to be recieved from the power 
meter per kWh.
Pulsed Input Setup
  Mode
  Pls/kWh