m2 Version 3.11  Manual  RS.8A.N5.02  ©  Danfoss  10-2007  31
EKC measurements and setup
Concept
The m2 display can display data from individual 
controllers. Data is uploaded to m2 via data com-
munication.
The following can be displayed, depending on the 
type of controller and what is being regulated:
The point number will correspond to a controller address
Supplementary text that can 
be added to the point number
Indicates the upper alarm limit setting.  When 
the    of the symbol is scrolling, it indicates 
that the upper alarm limit has been exceeded.
A wave
Indicates the set point for the EKC controller
Indicates the lower alarm limit setting.  When 
the  part of the symbol is scrolling, it 
indicates that the lower alarm limit has been 
exceeded.
Primary meas-
urement from 
the controller.
 
This shows the 
air temperature.
For a pack con-
trol it could be: 
P0 bar
 - Remote - alarms are based on controller settings.
  Alarm limits will be determined by the external controller. 
Some alarm limits are set as absolute values, others as a 
dierence to the set point. See controller data.
Regulation status is shown 
by means of icons, e.g.:
  - cooling
  - defrost
  - fans on
  - compressors on
Secondary measure-
ment from the 
controller.
 
This shows the de-
frost temperature.
For a pack control it 
could be: 
Pc bar