Par. No. # Parameter description Default value 4-set-up Change during opera-
tion
Conver-
sion index
Type
27-6* Digital Inputs
27-60 Terminal X66/1 Digital Input [0] No operation All set-ups TRUE - Uint8
27-61 Terminal X66/3 Digital Input [0] No operation All set-ups TRUE - Uint8
27-62 Terminal X66/5 Digital Input [0] No operation All set-ups TRUE - Uint8
27-63 Terminal X66/7 Digital Input [0] No operation All set-ups TRUE - Uint8
27-64 Terminal X66/9 Digital Input [0] No operation All set-ups TRUE - Uint8
27-65 Terminal X66/11 Digital Input [0] No operation All set-ups TRUE - Uint8
27-66 Terminal X66/13 Digital Input [0] No operation All set-ups TRUE - Uint8
27-7* Connections
27-70 Relay [0] Standard Relay 2 set-ups FALSE - Uint8
27-9* Readouts
27-91 Cascade Reference 0.0 % All set-ups TRUE -1 Int16
27-92 % Of Total Capacity 0 % All set-ups TRUE 0 Uint16
27-93 Cascade Option Status [0] Disabled All set-ups TRUE - Uint8
VLT
®
AQUA Drive
Operating Instructions
8. How to programme the frequency converter
MG.20.M5.02 - VLT
®
is a registered Danfoss trademark
137
8