ALARM 92, NoFlow:
A no load situation has been detected for the system. See parameter
group 22-2*.
ALARM 93, Dry Pump:
A no flow situation and high speed indicates that the pump has run dry.
See parameter group 22-2*
ALARM 94, End of Curve:
Feed back stays lower than the set point, which may be indicates a leak-
age in the pipe system. See parameter group 22-5*
ALARM 95, Broken Belt:
Torque is below the torque level set for no load indicating a broken belt.
See parameter group 22-6*
ALARM 96, Start Delayed:
Start of the motor has been delayed due to short cycle protection is ac-
tive. See parameter group 22-7*.
ALARM 250, New Spare Part:
The power or Switch Mode Power Supply has been exchanged. The fre-
quency converter type code must be restored in the EEPROM. Select the
correct type code in Par 14-23 according to the label on unit. Remember
to select ‘Save to EEPROM’ to complete.
ALARM 251, New Type Code:
The frequency converter has got a new type code.
9. Troubleshooting
VLT
®
AQUA Drive
Operating Instructions
146
MG.20.M5.02 - VLT
®
is a registered Danfoss trademark
9

Table of Contents

Other manuals for Danfoss VLT AQUA Drive FC 202

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AQUA Drive FC 202 and is the answer not in the manual?

Danfoss VLT AQUA Drive FC 202 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AQUA Drive FC 202
CategoryDC Drives
LanguageEnglish

Related product manuals