Page #155 background image
Normal overload 110% for 1 minute
Size: PK75 P1K1 P1K5 P2K2 P3K0 P3K7 P4K0 P5K5 P7K5 P11K P15K P18K P22K P30K P37K P45K P55K P75K P90K
Typical Shaft Output [kW] 0.75 1.1 1.5 2.2 3 3.7 4 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90
IP 20 / NEMA Chassis A2 A2 A2 A2 A2 A2 A2 A3 A3 B3 B3 B3 B4 B4 B4 C3 C3 C4 C4
IP 21 / NEMA 1 A2A2A2A2A2A2A2A3A3
B1 B1 B1 B2 B2 B2 C1 C1 C2 C2
IP 55 / NEMA 12 A5 A5 A5 A5 A5 A5 A5 A5 A5 B1 B1 B1 B2 B2 B2 C1 C1 C2 C2
IP 66
A5 A5 A5 A5 A5 A5 A5 A5 A5 B1 B1 B1 B2 B2 B2 C1 C1 C2 C2
Output current
Continuous
(3 x 525-550 V ) [A]
1.8 2.6 2.9 4.1 5.2 - 6.4 9.5 11.5
19 23 28 36 43 54 65 87 105 137
Intermittent
(3 x 525-550 V ) [A]
2.9 3.2 4.5 5.7 - 7.0 10.5 12.7 21 25 31 40 47 59 72 96 116 151
Continuous
(3 x 525-600 V ) [A]
1.7 2.4 2.7 3.9 4.9 - 6.1 9.0 11.0
18 22 27 34 41 52 62 83 100 131
Intermittent
(3 x 525-600 V ) [A]
2.6 3.0 4.3 5.4 - 6.7 9.9 12.1 20 24 30 37 45 57 68 91 110 144
Continuous kVA (525 V AC)
[kVA]
1.7 2.5 2.8 3.9 5.0 - 6.1 9.0 11.0
18.1 21.9 26.7 34.3 41 51.4 61.9 82.9 100 130.5
Continuous kVA (575 V AC)
[kVA]
1.7 2.4 2.7 3.9 4.9 - 6.1 9.0 11.0 17.9 21.9 26.9 33.9 40.8 51.8 61.7 82.7 99.6 130.5
Max. cable size
(mains, motor, brake)
[AWG]
2)
[mm
2
]
-
24 - 10 AWG
0.2 - 4
6
16
2
35
1
50
3/0
95
5)
Max. input current
Continuous
(3 x 525-600 V ) [A]
1.7 2.4 2.7 4.1 5.2 - 5.8 8.6 10.4 17.2 20.9 25.4 32.7 39 49 59 78.9 95.3 124.3
Intermittent
(3 x 525-600 V ) [A]
2.7 3.0 4.5 5.7 - 6.4 9.5 11.5 19 23 28 36 43 54 65 87 105 137
Max. pre-fuses
1)
[A]
10 10 10 20 20 - 20 32 32
Environment:
Estimated power loss
at rated max. load [W]
4)
35 50 65 92 122 - 145 195 261 225 285 329
Enclosure IP 20:
Weight
enclosure IP20 [kg]
6.5 6.5 6.5 6.5 6.5 - 6.5 6.6 6.6
12 12 12 23.5 23.5 23.5 35 35 50 50
Efficiency
4)
0.97 0.97 0.97 0.97 0.97 - 0.97 0.97 0.97 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98
Table 10.1:
5)
Motor and mains cable: 300MCM/150mm
2
10.1.5. Mains Supply 3 x 525 - 600 VAC
VLT
®
AQUA Drive
Operating Instructions
10. Specifications
MG.20.M5.02 - VLT
®
is a registered Danfoss trademark
155
10

Table of Contents

Other manuals for Danfoss VLT AQUA Drive FC 202

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AQUA Drive FC 202 and is the answer not in the manual?

Danfoss VLT AQUA Drive FC 202 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AQUA Drive FC 202
CategoryDC Drives
LanguageEnglish

Related product manuals