EasyManuals Logo

Danfoss VLT AQUA Drive FC 202 Operating Instructions

Danfoss VLT AQUA Drive FC 202
173 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #166 background imageLoading...
Page #166 background image
60 AVM - Pulse Width Modulation, 525 - 600 V
Illustration 10.17: Derating of I
out
for different T
AMB, MAX
for enclosure E
at 600 V, using 60 AVM in Normal torque mode (110% over torque).
SFAVM - Stator Frequency Asyncron Vector Modulation
Illustration 10.18: Derating of I
out
for different T
AMB, MAX
for enclosure E
at 600 V, using SFAVM in Normal torque mode (110% over torque).
10.2.3. Derating for Low Air Pressure
The cooling capability of air is decreased at lower air pressure.
At altitudes higher than 2 km, please contact Danfoss regarding PELV.
Below 1000 m altitude no derating is necessary but above 1000 m the ambient temperature (T
AMB
) or max. output current (I
out
) should be derated in
accordance with the shown diagram.
Illustration 10.19: Derating of output current versus altitude at T
AMB, MAX
. By altitudes above 2 km, please contact Danfoss regarding PELV.
An alternative is to lower the ambient temperature at high altitudes and thereby ensure 100% output current at high altitudes.
10. Specifications
VLT
®
AQUA Drive
Operating Instructions
166
MG.20.M5.02 - VLT
®
is a registered Danfoss trademark
10

Table of Contents

Other manuals for Danfoss VLT AQUA Drive FC 202

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AQUA Drive FC 202 and is the answer not in the manual?

Danfoss VLT AQUA Drive FC 202 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AQUA Drive FC 202
CategoryDC Drives
LanguageEnglish

Related product manuals