0-01 Language
Option: Function:
Defines the language to be used in the display.
[0]
*
English
1-20 Motor Power [kW]
Range: Function:
Size re-
lated
*
[0.09 - 500 kW] Enter the nominal motor power in kW according to the motor
nameplate data. The default value corresponds to the nominal
rated output of the unit.
This parameter cannot be adjusted while the motor is running.
Depending on the choices made in
par. 0-03 Regional Set-
tings
, either
par. 1-20 or par. 1-21 Motor Power
is made invisi-
ble.
1-21 Motor Power [HP]
Range: Function:
Size re-
lated
*
[0.09 - 500 HP] Enter the nominal motor power in HP according to the motor
nameplate data. The default value corresponds to the nominal
rated output of the unit.
This parameter cannot be adjusted while the motor is running.
Depending on the choices made in
par. 0-03 Regional Set-
tings
, either
par. 1-20 or par. 1-21 Motor Power
is made invisi-
ble.
1-22 Motor Voltage
Range: Function:
Size re-
lated
*
[10 - 1000 V] Enter the nominal motor voltage according to the motor name-
plate data. The default value corresponds to the nominal rated
output of the unit.
This parameter cannot be adjusted while the motor is running.
1-23 Motor Frequency
Range: Function:
Size re-
lated
*
[20 - 1000 Hz] Select the motor frequency value from the motor nameplate
data. For 87 Hz operation with 230/400 V motors, set the name-
plate data for 230 V/50 Hz. Adapt par. 4-13
Motor Speed High
Limit [RPM)
and par. 3-03
Maximum Reference
to the 87 Hz
application.
This parameter cannot be adjusted while the motor is running.
VLT
®
AQUA Drive Programming Guide 1. How to Programme
MG.20.O2.02 - VLT
®
is a registered Danfoss trademark
13
1

Other manuals for Danfoss vlt aqua

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss vlt aqua and is the answer not in the manual?

Danfoss vlt aqua Specifications

General IconGeneral
Supply Voltage200-240V, 380-500V, 525-600V
EnclosureIP20
FeaturesEnergy optimization
ApprovalsCE, UL, cUL
Input Voltage Range200-240V, 380-500V, 525-600V
Output Voltage Range0 to supply voltage
Protection FeaturesOvervoltage, Undervoltage, Overcurrent, Short circuit, Ground fault
Communication InterfacesPROFIBUS
Cooling MethodAir-cooled

Related product manuals