16-09 Custom Readout
Range: Function:
0.00
Custom-
Readou-
tUnit
*
[-999999.99 -
999999.99 Custom-
ReadoutUnit]
View the user-defined readouts as defined in par. 0-30, 0-31
and 0-32.
2.15.3. 16-1* Motor Status
Parameters for reading the motor status values.
16-10 Power [kW]
Range: Function:
0.0kW
*
[0.0 - 1000.0 kW] View the motor power in kW. The value shown is calculated on
the basis of the actual motor voltage and motor current. The
value is filtered, and therefore approx. 30 ms may pass from
when an input value changes to when the data read-out values
change.
16-11 Power [hp]
Range: Function:
0.00hp
*
[0.00 - 1000.00 hp] View the motor power in hp. The value shown is calculated on
the basis of the actual motor voltage and motor current. The
value is filtered, and therefore approx. 30 ms may pass from
when an input value changes to when the data read-out values
change.
16-12 Motor Voltage
Range: Function:
0.0V
*
[0.0 - 6000.0 V] View the motor voltage, a calculated value used for controlling
the motor.
16-13 Motor Frequency
Range: Function:
0.0Hz
*
[0.0 - 6500.0 Hz] View the motor frequency, without resonance dampening.
16-14 Motor Current
Range: Function:
0.00A
*
[0.00 - 0.00 A] View the motor current measured as a mean value, IRMS. The
value is filtered, and thus approx. 30 ms may pass from when
an input value changes to when the data read-out values
change.
2. Parameter Description VLT
®
AQUA Drive Programming Guide
162
MG.20.O2.02 - VLT
®
is a registered Danfoss trademark
2

Other manuals for Danfoss vlt aqua

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss vlt aqua and is the answer not in the manual?

Danfoss vlt aqua Specifications

General IconGeneral
Supply Voltage200-240V, 380-500V, 525-600V
EnclosureIP20
FeaturesEnergy optimization
ApprovalsCE, UL, cUL
Input Voltage Range200-240V, 380-500V, 525-600V
Output Voltage Range0 to supply voltage
Protection FeaturesOvervoltage, Undervoltage, Overcurrent, Short circuit, Ground fault
Communication InterfacesPROFIBUS
Cooling MethodAir-cooled

Related product manuals