If no flow is detected, the frequency converter will increase the set point for pressure to ensure
a slight over pressure in the system (boost to be set in par. 22-45,
Setpoint Boost
).
The feedback from the pressure transducer is monitored and when this pressure has dropped with
a set percentage below the normal set point for pressure (Pset), the motor will ramp up again and
pressure will be controlled for reaching the set value (Pset).
2) In systems where the pressure or temperature is controlled by an external PI controller, the
wake up conditions can not be based on feedback from the pressure/temperature transducer as
the setpoint is not known. In the example with a boost system, desired pressure Pset is not known.
Par. 1-00,
Configuration mode
, must be set for Open Loop.
Example: Boost system.
2. Parameter Description VLT
®
AQUA Drive Programming Guide
202
MG.20.O2.02 - VLT
®
is a registered Danfoss trademark
2

Other manuals for Danfoss vlt aqua

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss vlt aqua and is the answer not in the manual?

Danfoss vlt aqua Specifications

General IconGeneral
Supply Voltage200-240V, 380-500V, 525-600V
EnclosureIP20
FeaturesEnergy optimization
ApprovalsCE, UL, cUL
Input Voltage Range200-240V, 380-500V, 525-600V
Output Voltage Range0 to supply voltage
Protection FeaturesOvervoltage, Undervoltage, Overcurrent, Short circuit, Ground fault
Communication InterfacesPROFIBUS
Cooling MethodAir-cooled

Related product manuals