natively, the speed in RPM can be entered in par. 22-85 Speed
at Design Point [RPM]. If it has been decided to use Hz in par.
0-02, then par. 22-83 Speed No Flow [Hz] should also be used.
22-87 Pressure at No-Flow Speed
Range: Function:
0 Refer-
ence/
Feed-
back
Units
*
[0 - 999999.999]
Enter the pressure H
MIN
corresponding to Speed at No Flow in
Reference/Feedback Units.
22-88 Pressure at Rated Speed
Range: Function:
0 Refer-
ence/
Feed-
back
Units
*
[0 - 999999.999]
Enter the value corresponding to the Pressure at Rated Speed,
in Reference/Feedback Units. This value can be defined using
the pump datasheet.
22-90 Flow at Rated Speed
Range: Function:
0
*
[0 - 999999.999]
Enter the value corresponding to Flow at Rated Speed. This val-
ue can be defined using the pump datasheet.
VLT
®
AQUA Drive Programming Guide 2. Parameter Description
MG.20.O2.02 - VLT
®
is a registered Danfoss trademark
211
2

Other manuals for Danfoss vlt aqua

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss vlt aqua and is the answer not in the manual?

Danfoss vlt aqua Specifications

General IconGeneral
Supply Voltage200-240V, 380-500V, 525-600V
EnclosureIP20
FeaturesEnergy optimization
ApprovalsCE, UL, cUL
Input Voltage Range200-240V, 380-500V, 525-600V
Output Voltage Range0 to supply voltage
Protection FeaturesOvervoltage, Undervoltage, Overcurrent, Short circuit, Ground fault
Communication InterfacesPROFIBUS
Cooling MethodAir-cooled

Related product manuals