η
DESTAGE
= η
HIGH
η
DESTAGE
%
100
where n
HIGH
is Motor
Speed High Limit and n
DESTAGE100%
is the value of Destaging
Threshold.
25-47 Destaging Speed [Hz]
Option: Function:
Readout of the below calculated value for Destaging Speed.
When removing a fixed speed pump, in order to prevent an un-
dershoot of pressure, the variable speed pump ramps up to a
higher speed. When the variable speed pump reaches the “De-
staging Speed” the fixed speed pump is destaged. Destaging
Speed is calculated based on
Destaging Threshold
, par. 25-43,
and
Motor Speed High Limit [Hz]
, par. 4-14.
Destaging Speed is calculated with the following formula:
η
DESTAGE
= η
HIGH
η
DESTAGE
%
100
where n
HIGH
is Motor Speed High Limit and n
DESTAGE100%
is the
value of Destaging Threshold.
2.21.5. 25-5* Alternation Settings
Parameters for defining the conditions for alternation of the variable speed pump (lead), if selected
as part of the control strategy.
25-50 Lead Pump Alternation
Option: Function:
[0]
*
Off
[1] At Staging
VLT
®
AQUA Drive Programming Guide 2. Parameter Description
MG.20.O2.02 - VLT
®
is a registered Danfoss trademark
237
2

Other manuals for Danfoss vlt aqua

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss vlt aqua and is the answer not in the manual?

Danfoss vlt aqua Specifications

General IconGeneral
Supply Voltage200-240V, 380-500V, 525-600V
EnclosureIP20
FeaturesEnergy optimization
ApprovalsCE, UL, cUL
Input Voltage Range200-240V, 380-500V, 525-600V
Output Voltage Range0 to supply voltage
Protection FeaturesOvervoltage, Undervoltage, Overcurrent, Short circuit, Ground fault
Communication InterfacesPROFIBUS
Cooling MethodAir-cooled

Related product manuals