1. Disconnect from mains and wait until
the display turns off.
2a. Press [Status] - [Main Menu] - [OK]
at the same time while power up for
LCP 102, Graphical Display
2b. Press [Menu] while power up for LCP
101, Numerical Display
3. Release the keys after 5 s.
4. The frequency converter is now pro-
grammed according to default set-
tings.
This procedure initialises all except:
15-00
Operating Hours
15-03
Power-up's
15-04
Over temp's
15-05
Over volt's
NB!
When you carry out manual initialisation, you also reset serial communication, RFI
filter settings (par. 14-50) and fault log settings.
Removes parameters selected in
Personal Menu
.
NB!
After initialization and power cycling, the display will not show any information until
after a couple of minutes.
1. How to Programme VLT
®
AQUA Drive Programming Guide
24
MG.20.O2.02 - VLT
®
is a registered Danfoss trademark
1

Other manuals for Danfoss vlt aqua

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss vlt aqua and is the answer not in the manual?

Danfoss vlt aqua Specifications

General IconGeneral
Supply Voltage200-240V, 380-500V, 525-600V
EnclosureIP20
FeaturesEnergy optimization
ApprovalsCE, UL, cUL
Input Voltage Range200-240V, 380-500V, 525-600V
Output Voltage Range0 to supply voltage
Protection FeaturesOvervoltage, Undervoltage, Overcurrent, Short circuit, Ground fault
Communication InterfacesPROFIBUS
Cooling MethodAir-cooled

Related product manuals