3-11 Jog Speed [Hz]
Range: Function:
Size re-
lated
*
[0 - 1000 Hz] The jog speed is a fixed output speed at which the frequency
converter is running when the jog function is activated.
See also par. 3-80.
3-13 Reference Site
Option: Function:
Select which reference site to activate.
[0]
*
Linked to Hand / Auto Use local reference when in Hand mode; or remote reference
when in Auto mode.
[1] Remote Use remote reference in both Hand mode and Auto mode.
[2] Local Use local reference in both Hand mode and Auto mode.
3-14 Preset Relative Reference
Range: Function:
0.00%
*
[-200.00 - 200.00 %] The actual reference, X, is increased or decreased with the per-
centage Y, set in par.3-14. This results in the actual reference
Z. Actual reference (X) is the sum of the inputs selected in par.
3-15, Reference Source 1, par.3-16, Reference Source 2, par.
3-17, Reference Source 3, and par.8-02, Control Word Source.
2. Parameter Description VLT
®
AQUA Drive Programming Guide
62
MG.20.O2.02 - VLT
®