3-92 Power Restore
Option: Function:
[0]
*
Off Resets the Digital Potentiometer reference to 0% after power
up.
[1] On Restores the most recent Digital Potentiometer reference at
power up.
3-93 Maximum Limit
Range: Function:
100%
*
[-200 - 200 %] Set the maximum permissible value for the resultant reference.
This is advisable if the Digital Potentiometer is used for fine
tuning of the resulting reference.
3-94 Minimum Limit
Range: Function:
0%
*
[-200 - 200 %] Set the minimum permissible value for the resultant reference.
This is advisable if the Digital Potentiometer is used for fine
tuning of the resulting reference.
3-95 Ramp Delay
Range: Function:
1.000 s
*
[0.000 - 3600.00 s] Enter the delay required from activation of the digital potenti-
ometer function until the frequency converter starts to ramp the
reference. With a delay of 0 ms, the reference starts to ramp as
soon as INCREASE / DECREASE is activated. See also par. 3-91
Ramp Time
.