EasyManuals Logo

Danfoss vlt aqua Programming Guide

Danfoss vlt aqua
298 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #74 background imageLoading...
Page #74 background image
4-56 Warning Feedback Low
Option: Function:
[-99999
9.999]
*
-999999.999 -
999999.999
Enter the lower feedback limit. When the feedback falls below
this limit, the display reads Feedb Low. The signal outputs can
be programmed to produce a status signal on terminal 27 or 29
and on relay output 01 or 02.
4-57 Warning Feedback High
Range: Function:
999999.
999
*
[Par. 4-56 -
999999.999]
Enter the upper feedback limit. When the feedback exceeds this
limit, the display reads Feedb High. The signal outputs can be
programmed to produce a status signal on terminal 27 or 29 and
on relay output 01 or 02.
4-58 Missing Motor Phase Function
Option: Function:
[0] Off Displays an alarm in the event of a missing motor phase.
[1]
*
On No alarm displayed in the event of a missing motor phase. How-
ever, if the motor runs on only two phases, it can be damaged
by overheating. Retaining the
On
setting is therefore strongly
recommended.
This parameter cannot be adjusted while the motor is running.
2.6.4. 4-6* Speed Bypass
Define the Speed Bypass areas for the ramps.
Some systems call for avoiding certain output frequencies or speeds, due to resonance problems
in the system. A maximum of four frequency or speed ranges can be avoided.
4-60 Bypass Speed From [RPM]
Array [4]
0 RPM
*
[0 - par. 4-13 RPM] Some systems call for avoiding certain output speeds due to
resonance problems in the system. Enter the lower limits of the
speeds to be avoided.
4-61 Bypass Speed From [Hz]
Array [4]
0 Hz
*
[0 - par. 4-14 Hz] Some systems call for avoiding certain output speeds due to
resonance problems in the system. Enter the lower limits of the
speeds to be avoided.
2. Parameter Description VLT
®
AQUA Drive Programming Guide
74
MG.20.O2.02 - VLT
®
is a registered Danfoss trademark
2

Other manuals for Danfoss vlt aqua

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss vlt aqua and is the answer not in the manual?

Danfoss vlt aqua Specifications

General IconGeneral
Supply Voltage200-240V, 380-500V, 525-600V
EnclosureIP20
FeaturesEnergy optimization
ApprovalsCE, UL, cUL
Input Voltage Range200-240V, 380-500V, 525-600V
Output Voltage Range0 to supply voltage
Protection FeaturesOvervoltage, Undervoltage, Overcurrent, Short circuit, Ground fault
Communication InterfacesPROFIBUS
Cooling MethodAir-cooled

Related product manuals