EasyManua.ls Logo

Danfoss vlt aqua - Page 98

Danfoss vlt aqua
298 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2.8.4. 6-1* Analog Input 1
Parameters for configuring the scaling and limits for analog input 1 (terminal 53).
6-10 Terminal 53 Low Voltage
Range: Function:
0.07V
*
[0.00 - par. 6-11] Enter the low voltage value. This analog input scaling value
should correspond to the low reference/feedback value set in
par. 6-14.
6-11 Terminal 53 High Voltage
Range: Function:
10.0V
*
[Par. 6-10 to 10.0 V] Enter the high voltage value. This analog input scaling value
should correspond to the high reference/feedback value set in
par. 6-15.
6-12 Terminal 53 Low Current
Range: Function:
4 mA
*
[0.0 to par. 6-13 mA] Enter the low current value. This reference signal should corre-
spond to the low reference/feedback value, set in par. 6-14. The
value must be set at >2 mA in order to activate the Live Zero
Time-out Function in par. 6-01.
6-13 Terminal 53 High Current
Range: Function:
20.0
mA
*
[ Par. 6-12 to - 20.0
mA]
Enter the high current value corresponding to the high refer-
ence/feedback set in par. 6-15.
2. Parameter Description VLT
®
AQUA Drive Programming Guide
98
MG.20.O2.02 - VLT
®
is a registered Danfoss trademark
2

Other manuals for Danfoss vlt aqua

Related product manuals