9-67 Control Word 1
Range: Function:
0* [0 - 65535 ] This parameter accepts the Control Word from a Master Class 2 in the same format as PCD 1.
9-68 Status Word 1
Range: Function:
0* [0 - 65535 ] This parameter delivers the Status Word for a Master Class 2 in the same format as PCD 2.
9-70 Programming Set-up
Option: Function:
Select the set-up to be edited.
[0] Factory setup Uses default data. This option can be used as a data source to return the other set-ups to a known
state.
[1] Set-up 1 Edits Set-up 1.
[2] Set-up 2 Edits Set-up 2.
[3] Set-up 3 Edits Set-up 3.
[4] Set-up 4 Edits Set-up 4.
[9] * Active Set-up Follows the active set-up selected in par. 0-10
Active Set-up
.
This parameter is unique to LCP and fieldbuses. See also par. 0-11
Programming Set-up
.
9-71 Profibus Save Data Values
Option: Function:
Parameter values changed via Profibus are not automatically stored in non-volatile memory. Use
this parameter to activate a function that stores parameter values in the EEPROM non-volatile
memory, so changed parameter values will be retained at power-down.
[0] * Off Deactivates the non-volatile storage function.
[1] Store all setups Stores all parameter values for all set-ups in the non-volatile memory. The selection returns to
Off
[0] when all parameter values have been stored.
[2] Store all setups Stores all parameter values for all set-ups in the non-volatile memory. The selection returns to
Off
[0] when all parameter values have been stored.
9-72 ProfibusDriveReset
Option: Function:
[0] * No action
[1] Power-on reset Resets frequency converter upon power-up, as for power-cycle.
[3] Comm option reset Resets the Profibus option only, useful after changing certain settings in parameter group 9-**, e.g.
par. 9-18
Node Address
.
When reset, the frequency converter disappears from the fieldbus, which may cause a communi-
cation error from the master.
9-75 DO Identification
Range: Function:
0* [0 - 65535 ] Provides information about the DO (Drive Object).
FC 300 Programming Guide 3 Parameter descriptions