[4] Com cnt stop w/rst Same as [3] but after each precise stop the number of pulses counted during ramp down 0 rpm is
reset.
[5] Comp cnt stop w/o r Same as [3] but the number of pulses counted during ramp down to 0 rpm is deducted from the
counter value in par. 1-84
Precise Stop Counter Value
.
This parameter cannot be adjusted while the motor is running.
1-84 Precise Stop Counter Value
Range: Function:
100000* [0 - 999999999 ] Enter the counter value to be used in the integrated precise stop function, par. 1-83
Precise Stop
Function
.
The maximum permissible frequency at terminal 29 or 33 is 110 kHz.
1-85 Precise Stop Speed Compensation Delay
Range: Function:
10 ms* [0 - 100 ms] Enter the delay time for sensors, PLCs, etc. for use in par. 1-83
Precise Stop Function
. In speed
compensated stop mode, the delay time at different frequencies has a major influence on the stop
function.
3.3.9 1-9* Motor Temperature
Parameters for setting the temperature protection features for the motor.
1-90 Motor Thermal Protection
Option: Function:
The frequency converter determines the motor temperature for motor protection in three different
ways:
Via a thermistor sensor connected to one of the analog or digital inputs (par. 1-93
Ther-
mistor Source
). See section
PTC Thermistor Connection
.
Via a KTY sensor connected to an analog input (par. 1-96
KTY Thermistor Resource
). See
section
KTY Sensor Connection
.
Via calculation (ETR = Electronic Terminal Relay) of the thermal load, based on the actual
load and time. The calculated thermal load is compared with the rated motor current
I
M,N
and the rated motor frequency f
M,N
. The calculations estimate the need for a lower
load at lower speed due to less cooling from the fan incorporated in the motor.
[0] * No protection Continuously overloaded motor, when no warning or trip of the frequency converter is required.
[1] Thermistor warning Activates a warning when the connected thermistor or KTY-sensor in the motor reacts in the event
of motor over-temperature.
[2] Thermistor trip Stops (trips) frequency converter when connected thermistor or KTY sensor in the motor reacts in
the event of motor over-temperature.
The thermistor cut-out value must be > 3 k.
Integrate a thermistor (PTC sensor) in the motor for winding protection.
[3] ETR warning 1 Please see detailed description below
[4] ETR trip 1
[5] ETR warning 2
[6] ETR trip 2
[7] ETR warning 3
[8] ETR trip 3
[9] ETR warning 4
[10] ETR trip 4
FC 300 Programming Guide 3 Parameter descriptions
MG.33.M8.02 - VLT
®
is a registered Danfoss trademark
59
3

Other manuals for Danfoss VLT AutomationDrive FC 300

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 300 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 300 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 300
CategoryDC Drives
LanguageEnglish

Related product manuals