16-05 Main Actual Value [%]
-200 - 200 % *0 %
16-09 Custom Readout
0 - 9999 CustomReadoutUnit *0
CustomReadoutUnit
16-1* Motor Status
16-10 Power [kW]
0 - 1000 kW *0 kW
16-11 Power [hp]
0 - 1000 hp *0 hp
16-12 Motor Voltage
0 - 65535 V *0 V
16-13 Frequency
0 - 6553.5 Hz *0 Hz
16-14 Motor current
0 - 655.35 A *0 A
16-15 Frequency [%]
0 - 6553.5 % *0 %
16-16 Torque [Nm]
-30000 - 30000 Nm *0 Nm
16-17 Speed [RPM]
-30000 - 30000 RPM *0 RPM
16-18 Motor Thermal
0 - 100 % *0 %
16-22 Torque [%]
-200 - 200 % *0 %
16-3* Drive Status
16-30 DC Link Voltage
0 - 65535 V *0 V
16-33 Brake Energy /2 min
0 - 10000 kW *0 kW
16-34 Heatsink Temp.
-128 - 127 °C *0 °C
16-35 Inverter Thermal
0 - 255 % *0 %
16-36 Inv. Nom. Current
0 - 655.35 A *0 A
16-37 Inv. Max. Current
0 - 655.35 A *0 A
16-38 SL Controller State
0 - 20 *0
16-39 Control Card Temp.
0 - 65535 °C *0 °C
16-5* Ref. & Feedb.
16-50 External Reference
-200 - 200 % *0 %
16-52 Feedback[Unit]
-4999 - 4999 ProcessCtrlUnit *0
ProcessCtrlUnit
16-53 Digi Pot Reference
-200 - 200 *0
16-57 Feedback [RPM]
-30000 - 30000 RPM *0 RPM
16-6* Inputs & Outputs
16-60 Digital Input
0 - 65535 *0
16-61 Terminal 53 Setting
[0] Current mode
[1] Voltage mode
16-62 Analog input 53
0 - 20 *1
16-63 Terminal 54 Setting
[0] Current mode
[1] Voltage mode
16-64 Analog input 54
0 - 20 *1
16-65 Analog output 42 [mA]
0 - 20 mA *0 mA
16-66 Digital Output
0 - 15 *0
16-67 Pulse input 29 [Hz]
0 - 130000 *0
16-68 Pulse input 33 [Hz]
0 - 130000 *0
16-69 Pulse output 27 [Hz]
0 - 40000 *0
16-70 Pulse output 29 [Hz]
0 - 40000 *0
16-71 Relay output
0 - 65535 *0
16-72 Counter A
-32768 - 32767 *0
16-73 Counter B
-32768 - 32767 *0
16-79 Analog output 45 [mA]
0 - 20 mA *0 mA
16-8* Fieldbus & FC Port
16-80 Fieldbus CTW 1
0 - 65535 *0
16-82 Fieldbus REF 1
-32768 - 32767 *0
16-84 Comm. Option STW
0 - 65535 *0
16-85 FC Port CTW 1
0 - 65535 *1084
16-86 FC Port REF 1
-32768 - 32767 *0
16-9* Diagnosis Readouts
16-90 Alarm Word
0 - 0xFFFFFFFFUL *0
16-91 Alarm Word 2
0 - 0xFFFFFFFFUL *0
16-92 Warning Word
0 - 0xFFFFFFFFUL *0
16-93 Warning Word 2
0 - 0xFFFFFFFFUL *0
16-94 Ext. Status Word
0 - 0xFFFFFFFFUL *0
16-95 Ext. Status Word 2
0 - 0xFFFFFFFFUL *0
16-97 Alarm Word 3
0 - 0xFFFFFFFFUL *0
17-** Feedback Options
17-1* Inc.Enc.Interface
17-10 Signal Type
[0] None
*[1] RS422 (5V TTL)
[2] Sinusoidal 1Vpp
17-11 Resolution (PPR)
10 - 10000 *1024
17-5* Resolver Interface
17-50 Poles
2 - 2 *2
17-51 Input Voltage
2 - 8 V *7 V
17-52 Input Frequency
2 - 15 kHz *10 kHz
17-53 Transformation Ratio
0.1 - 1.1 *0.5
17-56 Encoder Sim. Resolution
*[0] Disabled
[1] 512
[2] 1024
[3] 2048
[4] 4096
17-59 Resolver Interface
*[0] Disabled
[1] Enabled
17-6* Monitoring and App.
17-60 Feedback Direction
*[0] Clockwise
[1] Counter clockwise
17-61 Feedback Signal Monitoring
[0] Disabled
*[1] Warning
[2] Trip
[3] Jog
[4] Freeze Output
[5] Max Speed
[6] Switch to Open Loop
18-** Data Readouts 2
18-8* Center Winder Readout
18-81 Tension PID Output
-5000 - 5000 Hz *0 Hz
18-82 Center Winder Output
-5000 - 5000 Hz *0 Hz
18-83 Line Speed
-5000 - 5000 Hz *0 Hz
18-84 Diameter
0 - 100 % *0 %
18-85 Tapered Tension Set Point
0 - 100 % *0 %
18-86 Tension Feedback
0 - 100 % *0 %
18-9* PID Readouts
18-90 Process PID Error
-200 - 200 % *0 %
18-91 Process PID Output
-200 - 200 % *0 %
18-92 Process PID Clamped Output
-200 - 200 % *0 %
18-93 Process PID Gain Scaled Output
-200 - 200 % *0 %
21-** Ext. Closed Loop
21-0* Ext. CL Autotuning
21-09 Extended PID Enable
*[0] Disabled
[1] Enabled Ext CL1 PID
21-1* Ext. CL 1 Ref./Fb.
21-11 Ext. 1 Minimum Reference
-999999.999 - 999999.999 ExtPID1Unit
*0 ExtPID1Unit
21-12 Ext. 1 Maximum Reference
-999999.999 - 999999.999 ExtPID1Unit
*100 ExtPID1Unit
21-13 Ext. 1 Reference Source
*[0] No function
[1] Analog Input 53
[2] Analog Input 54
[7] Frequency input 29
[8] Frequency input 33
21-14 Ext. 1 Feedback Source
*[0] No function
[1] Analog Input 53
[2] Analog Input 54
[3] Frequency input 29
[4] Frequency input 33
21-15 Ext. 1 Setpoint
-999999.999 - 999999.999 ExtPID1Unit
*0 ExtPID1Unit
21-17 Ext. 1 Reference [Unit]
-999999.999 - 999999.999 ExtPID1Unit
*0 ExtPID1Unit
21-18 Ext. 1 Feedback [Unit]
-999999.999 - 999999.999 ExtPID1Unit
*0 ExtPID1Unit
21-19 Ext. 1 Output [%]
0 - 100 % *0 %
21-2* Ext. CL 1 PID
21-20 Ext. 1 Normal/Inverse Control
*[0] Normal
[1] Inverse
21-21 Ext. 1 Proportional Gain
0 - 10 *0.01
21-22 Ext. 1 Integral Time
0.01 - 10000 s *10000 s
21-23 Ext. 1 Dierentation Time
0 - 10 s *0 s
21-24 Ext. 1 Dif. Gain Limit
1 - 50 *5
22-** Appl. Functions
22-0* Miscellaneous
22-02 Sleepmode CL Control Mode
*[0] Normal
[1] Simplied
22-4* Sleep Mode
22-40 Minimum Run Time
0 - 600 s *10 s
22-41 Minimum Sleep Time
0 - 600 s *10 s
22-43 Wake-Up Speed [Hz]
0 - 400.0 *10
22-44 Wake-Up Ref./FB Di
0 - 100 % *10 %
22-45 Setpoint Boost
-100 - 100 % *0 %
22-46 Maximum Boost Time
0 - 600 s *60 s
22-47 Sleep Speed [Hz]
0 - 400.0 *0
22-48 Sleep Delay Time
0 - 3600 s *0 s
22-49 Wake-Up Delay Time
0 - 3600 s *0 s
22-6* Broken Belt Detection
22-60 Broken Belt Function
*[0] O
[1] Warning
[2] Trip
22-61 Broken Belt Torque
5 - 100 % *10 %
22-62 Broken Belt Delay
0 - 600 s *10 s
30-** Special Features
30-2* Adv. Start Adjust
30-20 High Starting Torque Time [s]
0 - 60 s *Size related
30-21 High Starting Torque Current [%]
0 - 200.0 % *Size related
30-22 Locked Rotor Protection
*[0] O
[1] On
30-23 Locked Rotor Detection Time [s]
0.05 - 1 s *0.10 s
32-** Motion Control Basic Settings
32-1* User Unit
32-11 User Unit Denominator
1 - 65535 *1
32-12 User Unit Numerator
1 - 65535 *1
32-5* Feadback Source
32-50 Source Slave
*[0] 24V-Encoder
[1] MCB102
[2] MCB103
32-52 Source Master
[0] 24V-Encoder
*[1] MCB102
[2] MCB103
[3] VM
32-6* PID
32-60 Proportional factor
0.000 - 1000.000 *1.000
32-61 Derivative factor
0.000 - 1000.000 *0.000
32-62 Integral factor
0.0000 - 100.0000 *0.0000
32-63 Limit Value for Integral Sum[%]
0.0 - 100.0 % *100.0 %
32-64 PID Bandwidth[%]
0.0 - 100.0 % *100.0 %
32-65 Velocity Feed-Forward
0.000 - 100.000 *1.000
32-66 Acceleration Feed-Forward
0.000 - 100.000 *0.000
Appendix Quick Guide
MG06A702 Danfoss A/S © 03/2017 All rights reserved. 71
9 9

Other manuals for Danfoss VLT AutomationDrive FC 360

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 360 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 360 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 360
CategoryDC Drives
LanguageEnglish

Related product manuals