EasyManua.ls Logo

Danfoss VLT Compressor Drive CDS 803 - 7 RS485 Installation and Set-Up; Rs485; Overview

Danfoss VLT Compressor Drive CDS 803
82 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7 RS485 Installation and Set-up
7.1 RS485
7.1.1 Overview
RS485 is a 2-wire bus interface compatible with multi-drop network topology, that is, nodes can be connected as a bus, or
via drop cables from a common trunk line. A total of 32 nodes can be connected to 1 network segment.
Repeaters divide network segments, see Illustration 7.1.
Illustration 7.1 RS485 Bus Interface
NOTICE
Each repeater functions as a node within the segment in
which it is installed. Each node connected within a given
network must have a unique node address across all
segments.
Terminate each segment at both ends, using either the
termination switch (S801) of the frequency converters or a
biased termination resistor network. Always use screened
twisted pair (STP) cable for bus cabling, and follow good
common installation practice.
Low-impedance ground connection of the screen at every
node is important, including at high frequencies. Thus,
connect a large surface of the screen to ground, for
example with a cable clamp or a conductive cable gland. It
may be necessary to apply potential-equalising cables to
maintain the same earth potential throughout the network
- particularly in installations with long cables.
To prevent impedance mismatch, always use the same
type of cable throughout the entire network. When
connecting a motor to the frequency converter, always use
screened motor cable.
Cable Screened twisted pair (STP)
Impedance [Ω]
120
Cable length
[m]
Maximum 1200 (including drop lines)
Maximum 500 station-to-station
Table 7.1 Cable Specications
RS485 Installation and Set-... Design Guide
MG18N202 Danfoss A/S © 12/2015 All rights reserved. 49
7 7

Table of Contents