8.3 Acoustic Noise or Vibration
If the compressor or the equipment driven by the
compressor - for example, a fan - is making noise or
vibrations at certain frequencies, congure the following
parameters or parameter groups to reduce or eliminate the
noise or vibrations:
Parameter group 4-6* Speed Bypass.
Set parameter 14-03 Overmodulation to [0]
O.
Switching pattern and switching frequency
parameter group 14-0* Inverter Switching.
Parameter 1-64 Resonance Dampening.
The acoustic noise from the frequency converter comes
from 3 sources:
DC intermediate circuit coils
Integral fan
RFI lter choke
Enclosure Level [dBA]
H3 53.8
H4 64
H5 63.7
Table 8.3 Typical Values Measured at a Distance of 1 m
from the Unit
General Specications
VLT
®
Compressor Drive CDS 803
74 Danfoss A/S © 12/2015 All rights reserved. MG18N202