5.2.5 EMC Compliant Electrical Installation
General points to be observed to ensure EMC-correct electrical installation.
Use only shielded/armored motor cables and shielded/armored control cables.
Connect the screen to ground at both ends.
Avoid installation with twisted screen ends (pigtails), since this ruins the screening eect at high frequencies. Use
the cable clamps provided instead.
It is important to ensure good electrical contact from the installation plate through the installation screws to the
metal cabinet of the frequency converter.
Use star washers and galvanically conductive installation plates.
Do not use unshielded/unarmored motor cables in the installation cabinets.
How to Install Design Guide
MG18N202 Danfoss A/S © 12/2015 All rights reserved. 35