8 General Specications
8.1 Mains Supply Specications
8.1.1 Mains Supply 3x200–240 V AC
Frequency converter 4 TR/VZH028 5 TR/VZH035 6.5 TR/VZH044
Typical shaft output [kW] 6.0 7.5 10
IP20 enclosure protection rating H4 H4 H5
Maximum cable size in terminals (mains, compressor) [mm
2
/AWG]
16/6 16/6 16/6
Output current
Continuous
(3x200–240 V) [A]
20.7 25.9 33.7
Intermittent
(3x200–240 V) [A]
– – 37.1
Maximum input current
Continuous
3x200–240 V) [A]
23.0 28.3 37.0
Intermittent
(3x200–240 V) [A]
– – 41.5
Maximum mains fuses, see Table 5.6
Estimated power loss [W], Best case/typical
1)
182/
204
229/
268
369/
386
Weight enclosure protection P20 [kg/(lb)] 7.9 (17.4) 7.9 (17.4) 9.5 (21)
Eciency [%], best case/
typical
1)
97.3/
97.0
98.5/
97.1
97.2/
97.1
Table 8.1 3x200–240 V AC
1) At rated load conditions.
General Specications Design Guide
MG18N202 Danfoss A/S © 12/2015 All rights reserved. 69
8 8