3.12  Main Menu - Frequency Converter
Information - Group 15
Parameter group containing frequency converter
information
 
such as operating data, hardware configu-
ration and software versions.
3.12.1 15-0* Operating Data
15-00  Operating hours
Range: Function:
0 h*   [0 - 2147483647 h] View how many hours the frequency
converter 
has run. The value is saved
when the frequency converter is
turned off.
15-01  Running Hours
Range: Function:
0 h*   [0 - 2147483647
h]
View how many hours the motor has
run.
 
Reset the counter in 15-07 Reset
Running Hours Counter. The value is
saved when the frequency converter is
turned off.
15-02  kWh Counter
Range: Function:
0 kWh*   [0 - 2147483647
kWh]
Registering the power consumption
of the motor as a mean value over
one hour. Reset the counter in 
15-06 Reset kWh Counter.
15-03  Power Up's
Range: Function:
0 *   [0 - 2147483647 ] View the number of times the frequency
converter 
has been powered up.
15-04  Over Temp's
Range: Function:
0 *   [0 - 65535 ] View the number of frequency converter
temperature
 
faults which have occurred.
15-05  Over Volt's
Range: Function:
0 *   [0 - 65535 ] View the number of frequency converter
overvoltages 
which have occurred.
15-06  Reset kWh Counter
Option: Function:
[0] * Do not reset
Select [0]
 Do not reset 
if no reset of the kWh
counter is desired.
[1] Reset counter
Select [1] Reset 
and press [OK] to reset the
kWh counter to zero (see 15-02 kWh
Counter).
NOTE
The
 
reset is carried out by pressing [OK].
15-07  Reset Running Hours Counter
Option: Function:
[0] * Do not reset
Select [0]
 Do not reset 
if no reset of the
Running Hours counter is desired.
[1] Reset counter
Select [1] Reset counter 
and press [OK] to
reset the Running Hours counter
(15-01 Running Hours) and 15-08 Number of
Starts to zero (see also 15-01 Running Hours).
15-08  Number of Starts
Range: Function:
0 *   [0 - 2147483647 ] This is a read out parameter only. The
counter 
shows the numbers of starts
and stops caused by a normal Start/Stop
command and/or when entering/leaving
sleep mode.
NOTE
This 
parameter will be reset when resetting 15-07 Reset
Running Hours Counter.
3.12.2 15-1* Data Log Settings
The Data Log enables continuous logging of up to 4 data
sources 
(15-10 Logging Source) at individual rates
(15-11 Logging Interval). A trigger event (15-12 Trigger
Event) and window (15-14 Samples Before Trigger) are used
to start and stop the logging conditionally.
15-10  Logging Source
Array [4]
Option: Function:
Select which variables are to be
logged.
[0] * None
[1600] Control Word
[1601] Reference [Unit]
[1602] Reference [%]
[1603] Status Word
[1610] Power [kW]
[1611] Power [hp]
[1612] Motor Voltage
[1613] Frequency
[1614] Motor current
[1616] Torque [Nm]
[1617] Speed [RPM]
[1618] Motor Thermal
[1630] DC Link Voltage
[1632] Brake Energy /s
[1633] Brake Energy /2 min
[1634] Heatsink Temp.
Parameter Description
VLT
®
 Refrigeration Drive Programming Guide
MG16H102 - VLT
®
 is a registered Danfoss trademark
99