28-81 dP0 Offset
Range: Function:
the feedback is assumed to be a pressure
converted
to an equivalent temperature via
the pressure-to-temperature conversion
functions selectable in 20-01 Feedback 1
Conversion, 20-03 Feedback 2 Source or
20-06 Feedback 3 Source.
28-82 P0
Range: Function:
-999999.999 -
999999.999
[] The feedback pressure measured on
the
analogue inputs, converted to an
equivalent temperature.
28-83 P0 Setpoint
Range: Function:
-999999.999 -
999999.999
[] The setpoint of the frequency
converter
excluding any offset
programmed into 28-81 dP0 Offset.
28-84 P0 Reference
Range: Function:
-999999.999 -
999999.999
[] The sum of the setpoint of the
frequency
converter (28-83 P0 Setpoint)
and the offset programmed into
28-81 dP0 Offset.
28-85 P0 Minimum Reference
Range: Function:
-999999 -
999999
[] The largest negative offset value that can be
programmed
into 28-81 dP0 Offset without
exceeding the minimum reference value
programmed into 3-02 Minimum Reference. The
value is rounded to the nearest larger integer.
If a numerically larger value is entered the sum
of the offset and the setpoint is clipped to the
value of 3-02 Minimum Reference.
28-86 P0 Maximum Reference
Range: Function:
-999999 -
999999
[] The largest positive offset value that can be
programmed into 28-81 dP0 Offset without
exceeding the maximum reference value
programmed into 3-03 Maximum Reference. The
value is rounded to the nearest smaller integer.
If a numerically larger value is entered the sum
of the offset and the setpoint is clipped to the
value of 3-03 Maximum Reference.
3.21.4 28-9* Injection Control
The injection ON/OFF signal is a forced close signal to the
case
controllers (to turn display cases off). The signal is
distributed by following means- hardwired through a
digital output/relay or soft wired via bus by gateway or
system manager.
28-90 injection_on
Range: Function:
0* [0 - 1] This parameter is read by LON Bus to convey the
Injection
ON/OFF signal to the case controllers. If
this parameter value is 0 then it means Injection
OFF, if the parameter has a value 1 then it means
Injection ON.
28-91 Delayed Compressor Start
Range: Function:
0* [0 -
1]
If this parameter is set to 1, Delayed start of
compressor
is controlled by Injection Control feature
in association with 1-71 Start Delay. If it is set to 0
then Delayed start of compressor is controlled only by
1-71 Start Delay. If 28-91 Delayed Compressor Start set
to 1 and injection is OFF; start of compressor is
delayed by amount of time set in 1-71 Start Delay. If
28-91 Delayed Compressor Start set to1 and injection is
ON then start of compressor is not delayed. If 28-91 is
set to 0, Injection Controller feature will not interfere
in delaying start of compressor. Delayed start of
compressor is not active during Short Cycle
protection.
Parameter Description
VLT
®
Refrigeration Drive Programming Guide
166 MG16H102 - VLT
®
is a registered Danfoss trademark
33

Table of Contents

Other manuals for Danfoss VLT FC 103

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT FC 103 and is the answer not in the manual?

Danfoss VLT FC 103 Specifications

General IconGeneral
BrandDanfoss
ModelVLT FC 103
CategoryDC Drives
LanguageEnglish

Related product manuals