Manual initialisation
1. Disconnect from mains and wait until the display turns
off.
2a. Press [Status] - [Main Menu] - [OK] at the same time
while
 
power up for LCP 102, Graphical Display
2b. Press [Menu] while power up for LCP 101, Numerical
Display
3. Release the keys after 5 seconds
4. The frequency converter is now programmed according
to
 default settings.
This procedure initialises all except: 15-00 
Operating hours; 
15-03 Power Up's; 15-04 Over Temp's; 15-05 Over Volt's.
Table 2.7
NOTE
When 
you carry out manual initialisation, you also reset
serial communication, 14-50 RFI Filter and fault log settings.
Removes parameters selected in 25-00 Pack Controller.
NOTE
After
 
initialisation and power cycling, the display will not
show any information until after a couple of minutes.
How to Programme
VLT
®
 Refrigeration Drive Programming Guide
24 MG16H102 - VLT
®