Digital output
Programmable digital/pulse outputs 2
Terminal number 27, 29
1)
Voltage level at digital/frequency output 0-24 V
Max. output current (sink or source) 40 mA
Max. load at frequency output 1 k
Max. capacitive load at frequency output 10 nF
Minimum output frequency at frequency output 0 Hz
Maximum output frequency at frequency output 32 kHz
Accuracy of frequency output Max. error: 0.1% of full scale
Resolution of frequency outputs 12 bit
1) Terminal 27 and 29 can also be programmed as input.
The digital output is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
Control card, 24 V DC output
Terminal number 12, 13
Max. load 200 mA
The 24 V DC supply is galvanically isolated from the supply voltage (PELV), but has the same potential as the analog and digital
inputs and outputs.
Relay outputs
Programmable relay outputs 2
Relay 01 Terminal number
1-3 (break), 1-2 (make)
Max. terminal load (AC-1)
1)
on 1-2 (NO) (Resistive load)
2),3)
400 V AC, 2 A
Max. terminal load (AC-15)
1)
on 1-2 (NO) (Inductive load @ cosφ 0.4) 240 V AC, 0.2 A
Max. terminal load (DC-1)
1)
on 1-2 (NO) (Resistive load) 80 V DC, 2 A
Max. terminal load (DC-13)
1)
on 1-2 (NO) (Inductive load) 24 V DC, 0.1 A
Max. terminal load (AC-1)
1)
on 1-3 (NC) (Resistive load) 240 V AC, 2 A
Max. terminal load (AC-15)
1)
on 1-3 (NC) (Inductive load @ cosφ 0.4) 240 V AC, 0.2 A
Max. terminal load (DC-1)
1)
on 1-3 (NC) (Resistive load) 50 V DC, 2 A
Max. terminal load (DC-13)
1)
on 1-3 (NC) (Inductive load) 24 V DC, 0.1 A
Min. terminal load on 1-3 (NC), 1-2 (NO) 24 V DC 10 mA, 24V AC 2 mA
Environment according to EN 60664-1 overvoltage category III/pollution degree 2
Relay 02 Terminal number
4-6 (break), 4-5 (make)
Max. terminal load (AC-1)
1)
on 4-5 (NO) (Resistive load)
2)3)
400 V AC, 2 A
Max. terminal load (AC-15)
1)
on 4-5 (NO) (Inductive load @ cosφ 0.4) 240 V AC, 0.2 A
Max. terminal load (DC-1)
1)
on 4-5 (NO) (Resistive load) 80 V DC, 2 A
Max. terminal load (DC-13)
1)
on 4-5 (NO) (Inductive load) 24 V DC, 0.1 A
Max. terminal load (AC-1)
1)
on 4-6 (NC) (Resistive load) 240 V AC, 2 A
Max. terminal load (AC-15)
1)
on 4-6 (NC) (Inductive load @ cosφ 0.4) 240 V AC, 0.2 A
Max. terminal load (DC-1)
1)
on 4-6 (NC) (Resistive load) 50 V DC, 2 A
Max. terminal load (DC-13)
1)
on 4-6 (NC) (Inductive load) 24 V DC, 0.1 A
Min. terminal load on 4-6 (NC), 4-5 (NO) 24 V DC 10 mA, 24V AC 2 mA
Environment according to EN 60664-1 overvoltage category III/pollution degree 2
1) IEC 60947 t 4 and 5
The relay contacts are galvanically isolated from the rest of the circuit by reinforced isolation (PELV).
2) Overvoltage Category II
3) UL applications 300 V AC 2 A
Control card, 10 V DC output
Terminal number 50
Output voltage 10.5 V ±0.5 V
Max. load 25 mA
The 10 V DC supply is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
Specifications
Operating Instructions
100 Danfoss A/S © Rev. 05/2014 All rights reserved. MG16J202
1111

Table of Contents

Other manuals for Danfoss VLT FC 103

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT FC 103 and is the answer not in the manual?

Danfoss VLT FC 103 Specifications

General IconGeneral
BrandDanfoss
ModelVLT FC 103
CategoryDC Drives
LanguageEnglish

Related product manuals