D-500 MK2 User Manual Firmware V-6.3
- 133 -
Parameter Definition
Unit
Min
Max
Factory
Set
Description
Genset Active Power
Rate
kW
1
65000
100
It defines genset active power rating.
Genset Reactive Power
Rate
kVAr
1
65000
75
It defines genset reactive power rating.
Mains Active Power Rate
kW
0
65000
100
It defines mains transformer active
power rating.
Mains Reactive Power
Rate
kVAr
0
65000
75
It defines mains transformer reactive
power rating.
Unit Datalink Address
-
1
64
1
This parameter is used in order to force
data link addresses for fault free
operation with broken communication
wires.
Device Run/Stop Priority
-
1
64
1
This parameter defines the priority level
of D500 on the same data link.
Datalink Baud Rate
Kbps
0
4
3
0: 50 Kbps
1: 100 Kbps
2: 125 Kbps
3: 250 Kbps
4: 500 Kbps
Genset Number in Multi
Genset Systems
-
1
48
1
This is the number of synchronizing
gensets to the busbar.
Minimum Genset Fault
Action
-
0
4
0
This is action to be taken if the number
of available gensets is less than Genset
Number in Multi Genset Systems
0: not used
1: engine shutdown
2: load-dump alarm
3: warning
Mains Synch Unit
Number
-
0
16
0
This is the number of Mains
Synchronizing units in the system.
Master Change Delay
hour
0
255
0
This parameter defines the minimum
time period difference between two
master change operations in equal
aging.
Multi Genset Start-Up
Options
-
0
2
0
This parameter determines the number
of gensets to start, when there is a
REMOTE START signal.
0: Run With Start Power when Remote
Start signal arrives
1: Run With Mains Power when Remote
Start signal arrives
2: Run all available gensets when
remote start signal arrives
Multi Genset Start-Up
Power
kW
0
65000
100
This parameter decides the number of
gensets to start. If the total power of
starting gensets is less than this limit,
then a TOO FEW GENSETS warning
will occur.
Insufficient Multi Genset
Start-Up Power Alarm
Level
-
0
3
3
0: not used
1: engine shutdown
2: load-dump alarm
3: warning
17.17. SYNCHRONIZATION PARAMETERS