D-500 MK2 User Manual Firmware V-6.3
- 89 -
Synchronization Fail
Set if the phase and voltage synchronization is not successful before the
expiration of Synchronization Fail Timeout
Busbar Voltage Fail
Set if busbar voltages are not within limits and busbar voltage above Dead
Bus Limit during 5 seconds, when the master requests the slave to close
the genset contactor to the busbar.
Busbar Freq. Fail
Set if busbar frequency is not within limits and busbar voltage above Dead
Bus Limit during 5 seconds, when the master requests the slave to close
the genset contactor to the busbar.