D-500 MK3 User Manual Firmware V-14.2
- 115 -
Parameter Definition
Unit
Min
Max
Factory
Set
Description
Capacitive Overload Lim.
kvar
0
65000
0
If the total genset capacitive reactive
power goes over this limit when feeding
the load, this will generate a genset
over capacitive alarm.
Inductive Overload Lim.
kvar
0
65000
0
If the total genset inductive reactive
power goes over this limit when feeding
the load, this will generate a genset
over capacitive alarm.
Reactive Overload Timer
sec
0
120
3
If the genset reactive power is over the
limit during this timer, an overload fault
will occur.